HAT833 Series Three Power ATS Controller User Manual Page 18 of 56
The indication information will continuously display for 2s after it is active.
Table 15 – Indication Information
No.
Item
Description
1
Please Reset The
Alarm
When there is fault alarm occurs, the indication will be displayed when
change the genset mode to Auto Mode manually.
2
S1 Already Closed.
After S1 was already closed, the indication will be displayed when “S1
close (IOO)” button is pressed.
3
S2 Already Closed.
After S2 was already closed, the indication will be displayed when “S2
close (OIO)” button is pressed.
4
S3 Already Closed.
After S3 was already closed, the indication will be displayed when “S3
close (OOI)” button is pressed.
5
Panel Locked
The information displays when panel lock is active and keys are
pressed (Manual/Auto, IOO, OIO, OOI, OOO and Test keys).
Table 16 – Other Status Information
No.
Item
Description
1
Start Inhibit
Genset start Inhibit is active.
2
S1 Load Inhibit
S1 Load Inhibit input is active.
3
S2 Load Inhibit
S2 Load Inhibit input is active.
4
S3 Load Inhibit
S3 Load Inhibit input is active.
5
NEL 1 Trip
NEL1 off load signal is output.
6
NEL2 Trip
NEL2 off load signal is output.
7
NEL3 Trip
NEL3 off load signal is output.
8
Remote Gen On Load Remote start (on load) signal is active.
9
Remote Gen Off Load Remote start (off load) signal is active.
10
Gen Start Mains NG
Start genset when mains is abnormal.
11
Gen Start Master
Start when the gens supply and switching to highest priority.
12
Auto Mode
Current mode is Auto mode.
13
Manual Mode
Current mode is Manual mode.
14
Local Mode
Current mode is Local mode.