HAT828 High Speed ATS Controller User Manual Page 26 of 56
No.
Item
Range
Default
Description
Generator Setting
1
Start Delay
(0-9999)s
1
When the genset is ready to start, start
delay begins, after the delay has expired,
start signal will be initiated.
2
Stop Delay
(0-9999)s
5
When the genset is ready to stop, stop
delay begins, after the delay has expired,
start signal will be disconnected.
3
Two Gensets Start
Mode
(0~3)
0
0: Cycle Run;
1: Master-Slave Run;
2: Balanced Run;
3: None.
4
S1 Cycle Run Time
(0~9999)min
720
Gens cycle start S1 running time.
5
S2 Cycle Run Time
(0~9999)min
720
Gens cycle start S2 running time.
6
Supply Delay
(0~9999)s
120
When the start signal is active, the start
delay will be initiated. If the gen voltage
lasts abnormal after the delay has
expired, genset fault alarm will be
initiated.
7
Battery Volt Detect
(0~1)
0
0: Disable ; 1: Enable
8
Battery Under Volt
Warn
(0~1)
0
0: Disable ; 1: Enable
9
Set Value
(0~100.0)V
10.0
“Battery Under Volt” alarm will be
initiated if the battery voltage has fallen
below the set value.
10
Return Value
(0~100.0)V
10.5
“Battery Under Volt” alarm will be
removed if the battery voltage has
exceeded the set value.
11
Battery Over Volt
Warn
(0~1)
0
0: Disable ; 1: Enable
12
Set Value
(0~100.0)V
30.0
“Battery Over Volt” alarm will be initiated
if the battery voltage has exceeded the
set value.
13
Return Value
(0~100.0)V
29.5
“Battery Over Volt” alarm will be
removed if the battery voltage has fallen
below the set value.
Scheduled Run/Not Run Setting