HAT828 High Speed ATS Controller User Manual Page 22 of 56
8
PARAMETERS CONFIGURATION
8.1
ILLUSTRATION
In the main interface, press
key, choose
Configuration
and press
again to enter
into password confirmation interface. If password is correct, enter into parameter setting interface,
otherwise, exit to main interface directly. Factory default password is
01234
. In parameters
configuration interface, pressing
key to return the previous menu.
8.2
PARAMETERS CONFIGURATION
Table 16 – Parameters Configuration
No.
Item
Range
Default
Description
AC Setting
1
S1 Volt Normal
(0-3600)s
10
The delay from S1 voltage abnormal to
normal.
2
S1 Volt Abnormal
(0-3600)s
5
The delay from S1 voltage normal to
abnormal.
3
S2 Volt Normal
(0-3600)s
10
The delay from S2 voltage abnormal to
normal.
4
S2 Volt Abnormal
(0-3600)s
5
The delay from S2 voltage normal to
abnormal.
5
Master Set
(0~1)
0
0: S1 1: S2
6
System Type
(0~3)
6
0: S1 Mains S2 Gen;
1: S1 Gen S2 Mains;
2: S1 Mains S2 Mains;
3: S1 Gen S2 Gen.
7
AC System
(0~3)
0
0: 3 Phase 4 Wire (3P4W)
1: 3 Phase 3 Wire (3P3W)
2: 2 Phase 3 Wire (2P3W)
3: Single Phase 2 Wire (1P2W)
8
PT Fitted
(0~1)
0
0: Disable 1: Enable
9
PT Primary Volt
(30~30000)V
100
Primary voltage of voltage transformer
ratio.
10
PT Secondary Volt
(30~1000)V
100
Secondary
voltage
of
voltage
transformer ratio.
11
Rated Voltage
(0~30000)V
220
Rated voltage of AC system.
12
Over Volt Warn
(0~1)
1
0: Disable 1: Enable