HAT828 High Speed ATS Controller User Manual Page 32 of 56
No.
Item
Range
Default
Description
51
Combined 6 or Out 1
Active Type
(0~1)
0
0: Output (NO)
1: Output (NC)
52
Combined 6 or Out 1
Contents Setting
(0~99)
0
Not Used.
53
Combined 6 or Out 2
Active Type
(0~1)
0
0: Output (NO)
1: Output (NC)
54
Combined 6 or Out 2
Contents Setting
(0~99)
0
Not Used.
55
Combined 6 and Out
Active Type
(0~1)
0
0: Output (NO)
1: Output (NC)
56
Combined 6 and Out
Contents Setting
(0~99)
0
Not Used.
Module Setting
1
Power On Mode
(0-2)
0
0: Last Mode (Keep the working mode
last time running);
1: Manual Mode;
2: Auto Mode.
2
Language
(0~2)
0
0: Simplified Chinese;
1: English;
2: Other (Language can be set via PC
software, Default:
Traditional Chinese).
3
Password
(00000~65535) 01234
Password for entering parameters
setting.
4
Module Address
(1~254)
1
RS485 communication address.
5
RS485-1 Baud Rate
(0~3)
2
0: 2400bps;
1: 4800bps;
2: 9600bps;
3: 19200bps.
6
RS485-1 Stop Bit
(1~2)
2
2 stop bits or 1 stop bit can be set.
7
RS485-1 Parity Bit
(0~2)
0
0: None;
1: Odd Parity;
2: Even Parity.
8
RS485-2 Baud Rate
(0~3)
2
0: 2400bps;
1: 4800bps;
2: 9600bps;
3: 19200bps.