HAT160 ATS CONTROLLER USER MANUAL
HAT160 ATS Controller 2020-03-14 Version 1.1 Page 14 of 21
7.
DEFINITION AND RANGE OF PARAMETERS
Table 7 Parameter Setting Contents and Range (1)
No.
Items
Range
Default
Description
1
Priority
(1-3)
1
1: 1# priority
2: 2# priority
3: Spare to each other
2
1# Volt Abnormal
Delay
(1-7)
2 (5s)
1: 1s
2: 5s
3: 10s
4: 20s
5: 30s
6: 45s
7: User defined(Default: 5s)
3
2# Volt Abnormal
Delay
(1-7)
2 (5s)
1: 1s
2: 5s
3: 10s
4: 20s
5: 30s
6: 45s
7: User defined(Default: 5s)
4
Start Delay
(1-7)
4 (30s) 1: 3s
2: 8s
3: 15s
4: 30s
5: 50s
6: 70s
7: User defined(Default: 1s)
5
Stop Delay
(1-7)
6 (70s) 1: 3s
2: 8s
3: 15s
4: 30s
5: 50s
6: 70s
7: User defined(Default: 90s)
6
Open Delay
(1-7)
3 (5s)
1: 1s
2: 3s
3: 5s
4: 8s
5: 10s
6: 15s
7: User defined(Default: 5s)
7 Close Delay
(1-7)
3 (5s)
1: 1s