HAT160 ATS CONTROLLER USER MANUAL 

HAT160 ATS Controller                  2020-03-14                  Version 1.1            Page 13 of 21 

 

Fig. 7 Programming via LINK 

 

 
 
 
 
 
 
 
 

Summary of Contents for HAT160

Page 1: ...HAT160 ATS CONTROLLER USER MANUAL HAT160 ATS Controller 2020 03 14 Version 1 1 Page 1 of 21 HAT160 ATS CONTROLLER USER MANUAL SMARTGEN ZHENGZHOU TECHNOLOGY CO LTD ...

Page 2: ...m including photocopying or storing in any medium by electronic means or other without the written permission of the copyright holder SmartGen Technology reserves the right to change the contents of this document without prior notice Table 1 Software Version Date Version Content 2015 12 09 1 0 Original release 2020 03 14 1 1 Fixed description errors Table 2 Sign Illustration Symbol Instruction NOT...

Page 3: ... FUNCTION DESCRIPTION 7 4 3 INDICATOR DESCRIPTION 8 4 4 OPERATION 8 5 ALARMS 9 5 1 CLOSE OPEN FAULT ALARM 9 5 2 EXTERNAL INPUT FIRE RESET INPUT ALARM 9 5 3 ALARM RESET 9 6 CONNECTION 10 7 DEFINITION AND RANGE OF PARAMETERS 14 8 PARAMETERS SETTING 17 8 1 PARAMETERS SETTING MODE 17 8 2 PARAMETERS SETTING 17 8 3 RESET TO DEFAULT 17 9 TYPICAL APPLICATION 18 10 VERALL DIMENSION AND PANEL CUTOUT 19 11 T...

Page 4: ...nt for occurred voltage abnormal such as over voltage under voltage over frequency under frequency and loss of phase then control ATS transfer after delay When ATS switch gets abnormal controller can detect close open failure and indicates alarm on the front panel to ensure the correct action of ATS If I power gets abnormal controller can send signal to start genset Controller can realize remote c...

Page 5: ... parameters can be set from front panel Re closing function for power off Over close delay function and delay time is 0 5s If A phase voltage of any one way is normal controller can control ATS to act Under the circumstance of A phase voltage of any one way is normal if 2 way power voltages are abnormal at the same time ATS will automatically transfer to breaking neutral position Forced open input...

Page 6: ...A AC250V Volts free output Normally close 1 Close Relay 7A AC250V Volts free output Normally open 2 Close Relay 7A AC250V Volts free output Normally open LO NO Relay Output 7A AC250V Communication LINK interface MODBUS RTU Protocol Case Dimensions 86 9mmx158mmx119 5mm Panel Cutout 73 5mmx144mm Working Conditions Temperature 25 70 C Humidity 20 93 RH Storage Condition Temperature 25 70 C Protection...

Page 7: ...al mode switch Enter into lamp test status by pressing for 3s Enter into parameter configuration mode by pressing for 5s 1 Close 1 Close in Manual mode Adjust parameters in parameter configuration mode Open Open in Manual mode Adjust parameters in parameter configuration mode Clear alarm status close open failure auxiliary input alarm if alarms occur in Manual or Auto mode 2 Close Confirm 2 Close ...

Page 8: ...Alarm Indicator Lamp illuminates 1 or 2 Close Open fault Lamp flashes Auxiliary input alarm Fire Reset input is active Auto Mode Indicator Lamp illuminates controller in Auto mode Manual Mode Indicator Lamp illuminates controller in Manual mode Lamp flashes enter into parameter configuration mode NOTE Lamp flash frequency 1Hz 4 4 OPERATION When the controller is normally working in manual mode pre...

Page 9: ... FIRE RESET INPUT ALARM When auxiliary alarm input signal or fire reset input signal is detected the front panel alarm indicator will flash 1Hz meanwhile the ATS transfers to Breaking Middle Position and alarm will be locked 5 3 ALARM RESET If Close Open alarms in auto mode occur press to clear alarm the indicator will be extinguished at the same time the controller will Close Open again after 3s ...

Page 10: ...HAT160 ATS CONTROLLER USER MANUAL HAT160 ATS Controller 2020 03 14 Version 1 1 Page 10 of 21 6 CONNECTION Fig 3 Controller Side Panel ...

Page 11: ...ctive when close voltage falls below 65 of rated voltage close signal is inactive Q2O 2 Close Input Connect to auxiliary normally open contact of 2 power AC voltage input When close voltage reaches 70 of rated voltage close signal is active when close voltage falls below 65 of rated voltage close signal is inactive LO ATS Supply Output Output voltage after transfer of 2 way power A Phase and N Pha...

Page 12: ...HAT160 ATS CONTROLLER USER MANUAL HAT160 ATS Controller 2020 03 14 Version 1 1 Page 12 of 21 Fig 5 Terminals Changing Fig 6 Fuse Changing ...

Page 13: ...HAT160 ATS CONTROLLER USER MANUAL HAT160 ATS Controller 2020 03 14 Version 1 1 Page 13 of 21 Fig 7 Programming via LINK ...

Page 14: ...ch other 2 1 Volt Abnormal Delay 1 7 2 5s 1 1s 2 5s 3 10s 4 20s 5 30s 6 45s 7 User defined Default 5s 3 2 Volt Abnormal Delay 1 7 2 5s 1 1s 2 5s 3 10s 4 20s 5 30s 6 45s 7 User defined Default 5s 4 Start Delay 1 7 4 30s 1 3s 2 8s 3 15s 4 30s 5 50s 6 70s 7 User defined Default 1s 5 Stop Delay 1 7 6 70s 1 3s 2 8s 3 15s 4 30s 5 50s 6 70s 7 User defined Default 90s 6 Open Delay 1 7 3 5s 1 1s 2 3s 3 5s ...

Page 15: ...ay 1 7 2 5s 1 1s 2 5s 3 10s 4 20s 5 30s 6 45s 7 User defined Default 5s 10 2 Volt Normal Delay 1 7 2 5s 1 1s 2 5s 3 10s 4 20s 5 30s 6 45s 7 User defined Default 5s NOTE a Parameter values in this form can be set from control front panel or computer software b When delay value is set to 7 User defined you must set delay value via computer software If computer software is never used to set parameter...

Page 16: ... 1 1 0 Disabled 1 Enabled 5 Over Volt Threshold 100 120 115 Threshold 6 Over Volt Return 100 120 113 Return 7 Under Volt Monitor Enabled 0 1 1 0 Disabled 1 Enabled 8 Under Volt Threshold 70 100 75 Threshold 9 Under Volt Return 70 100 77 Return 10 Over Freq Monitor Enabled 0 1 1 0 Disabled 1 Enabled 11 Over Freq Threshold 100 120 110 Threshold 12 Over Freq Return 100 120 104 Return 13 Under Freq Mo...

Page 17: ...umber which needs to adjust by pressing and 2 Enter into setting status by pressing and illuminated indicators of flashes 3 After setting this parameter by pressing and save the values by pressing NOTE 1 Please refer to Chapter 7 for parameter list Table 7 Parameter Setting Contents and Range 2 the No in the table is the setting item number NOTE 2 In setting process discontinue present setting by ...

Page 18: ...ED Indicators Value No LED Indicators Value 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 9 10 9 TYPICAL APPLICATION Fig 9 Typical Application Diagram CAUTION 1 If ATS has trip function then it must be connected to AL port AC Volt input 2 Ensure 1 and 2 A phase won t be abnormal at the same time otherwise the controller won t send Close Open signal ...

Page 19: ...DIMENSION AND PANEL CUTOUT 10 1CASE DIMENSION Unit mm Fig 10 Case Dimension and Size 10 2INSTALLATION CUTOUT The controller has three installation ways panel built in internal 35mm slideway and internal screw mounting Panel built in and internal screw mounting sizes are as below Fig 11 Installation Size ...

Page 20: ...HAT160 ATS CONTROLLER USER MANUAL HAT160 ATS Controller 2020 03 14 Version 1 1 Page 20 of 21 10 3INSTALLATION a Fixing Clips b 35mm Slideway c Screw Mounting ...

Page 21: ...heck the connections between controller and ATS 1 or 2 power lamp flashes Check whether AC voltage is normal or not Alarm lamp flashes Remove trip status of the switch and reset alarm Alarm lamp illuminates Check the connections between controller and ATS Check if auxiliary contact is reliably connected Check Close Open delay value appropriately increase the value Genset failed to stop when switch...