APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 16 of 62
>
Start Delay
>
Stop Delay
>
Preheat Delay
00008
Form5: Press to change cursor
position,
are used for
changing cursor value,
Confirm
setting (form 4),
exit setting (form
4).
>
Cranking Time
>
Crank Rest Time
>
Safety On Time
>
Start Idle Time
>
Warming Up Time
>
Cooling Time
>
Stop Idle Time
>
ETS Hold Time
>
Start Delay
>
Stop Delay
>
Preheat Delay
00008
Form 6:
are used for
changing the setting contents.
Confirm setting (form 4),
to return
to previous menu. (form 1).
>
Cranking Time
>
Crank Rest Time
>
Safety On Time
>
Start Idle Time
>
Warming Up Time
>
Cooling Time
>
Stop Idle Time
>
ETS Hold Time
>
Wait Stop Time
NOTE:
Pressing
can exit setting directly during setting.
4.4 AUTO START/STOP OPERATION
Auto mode is selected by pressing the
button; a LED besides the button will
illuminate to confirm the operation.
Automatic Start Sequence:
1. When
“Remote Start” is active, “Start Delay” timer is initiated;
2. When start delay is over, preheat relay energizes (if configured
), “preheat delay XX s”
information will be displayed on LCD;
3. After the above delay, the Fuel Relay is energized, and then one second later, the
Start Relay is engaged. The engine is cranked for a pre-set time. If the pump unit fails
to fire during this cranking attempt then the fuel relay and start relay are disengaged
for the pre-
set rest period; “crank rest time” begins and wait for the next crank
attempt.
4. Should this start sequence continue beyond the set number of attempts, the start