APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 31 of 62
No.
Items
Parameter
Default
Description
1
Curve Type
(0-15)
7
SGX. See form 5.
2
Open Circuit
Action
(0-2)
0
0: Warn; 1: Shutdown; 2: No action
3
High Temp.
Shutdown
(0~300)ºC
98
Shutdown when external sensor
temperature is higher than this
value. Detecting only after safety
delay is over. The delay value can
be set.
4
High Temp.
Warn
(0~300)ºC
95
Warn
when
external
sensor
temperature is higher than this
value. Detecting only after safety
delay is over. The delay value and
return value can be set.
5
Low
Temp.
Warn
(0-1)
0
0: Disable
;
1: Enable
6
Custom
Curve
Users should set the corresponding
curve when select resistor curve
type or current curve type.
Oil Pressure Sensor
1
Curve Type
(0-15)
7
SGX. See form 5.
2
Open Circuit
Action
(0-2)
0
0: Warn; 1: Shutdown; 2: No action
3
Low
OP
Shutdown
(0-1000)kPa
103
Shutdown
when
external
oil
pressure is lower than this value.
Detecting only after safety delay is
over. The delay value can be set.
4
Low
OP
Warn
(0-1000)kPa
124
Warn when external oil pressure is
higher than this value. Detecting
only after safety delay is over. The
delay value and return value can be
set.
5
Custom
Curve
Users should set the corresponding
curve when select resistor curve
type or current curve type.
Liquid Level Sensor
1
Curve Type
(0-15)
4
SGH. See form 5.
2
Open Circuit
Action
(0-2)
0
0:Warn; 1:Shutdown; 2:No action
3
Low
Level
Warn
(0-1000)%
10
Warn when external level is lower
than this value. It is detecting all the
time. The delay value and return
value can be set.
4
Custom
Users should set the corresponding