APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 30 of 62
No.
Items
Parameter
Default
Description
Fail
D+(WL) voltage under this value,
charge failure alarms.
18
Start
Attempts
(1-10) times
3
Max. Crank times of crank attempts.
When reach this number, controller
will send start failure signal.
19
Crank
Disconnect
(0-2)
2
See form 5.
There
are
3
conditions
of
disconnecting starter with engine.
Each condition can be used alone
and simultaneously to separating the
start motor and genset as soon as
possible.
20
Disconnect
Engine
Speed
(0-1000)%
24%
Setting value is percentage of rated
speed. When engine speed is higher
than the set value, starter will be
disconnected. See the following
Installation Instruction.
21
Disconnect
Oil Pressure
(0-1000)kPa
200
When generator oil pressure is
higher than the set value, starter will
be disconnected. See the following
Installation Instruction.
22
After Unload
Idle
(0-1)
0
0: Disable
;
1: Enable Active when
system is in manual mode. After start
the unit, it is enter into idle running
when the unit is not on-load.
Module Setting
1
Power
on
Mode
(0-2)
0
0: Stop mode 1: Manual mode 2:
Auto mode
2
Module
Address
(1-254)
1
Controll
er’s address during remote
sensing.
3
Stop Bits
(0-1)
0
0: 2 stop bits; 1: 1 stop bit
4
Language
(0-2)
0
0: Simplified Chinese 1: English
2: Others
5
Password
(0-65535)
00318
For entering advanced parameters
setting.
Scheduling And Maintenance Setting
1
Scheduled
Run
(0-1)
0
0: Disable
;
1: Enable
2
Scheduled
Not Run
(0-1)
0
0: Disable
;
1: Enable
3
Maintenance (0-1)
0
0: Disable
;
1: Enable