4 OPERATION
LPC-2.SM7 can be in one of two operational modes - normal or error. When LPC-2.SM7 is in normal
mode, module parameters can be read or written via Smarteh IDE software.
4.1 Operational modes
Normal
Communication with the main module is working. Only green “PWR” LED2 is turned on.
Error
In case of communication fault, red “ERR” LED1 will turn on.
4.2 Parameters
If parameter is set to logical “1”, is considered to be active, enabled or set. If parameter has logical
value “0” is considered to be inactive, disabled or cleared.
Parameter can be a command or feedback. When parameter is marked as feedback it means that
LPC-2.SM7 is sending information to the main module. On the other hand, command represents
request from the main module to the LPC-2.SM7.
Command:
IR command number selection for transmit
[oIrCmdSendNum]
:
This parameter is used to
select the IR learned command which will be used for transmit.
Type: WORD
Raw to engineering data:
1 .. 15 IR transmit command 1 .. IR transmit command 15
→
IR command transmit control bit
[oIrCmdSend]
:
When this bit goes to "1", selected IR
command in o
IrCmdSendNum
is transmitted.
Type: BOOL
Raw to engineering data:
“0” No transmit
→
“1” Transmit selected IR command
→
IR protocol selector
[oIrProtocolSel]
:
Selector for IR receive protocol.
Type: WORD
Raw to engineering data:
0 Learned IR commands
→
1 RC-5 IR protocol
→
Feedback:
Actual light intensity value
[iLight]
:
Actual measured light intensity value.
Type: WORD
Raw to engineering data:
0 .. 1490 0 .. 1490 lux
→
Grid-eye minimum actual temperature value
[iGEyeMin]
:
Actual minimal temperature
value measured by IR matrix sensor.
Type: WORD
Raw to engineering data:
0 .. 12000 0 .. 120.00
→
°C
Grid-eye maximum actual temperature value
[iGEyeMax]
:
Actual maximum temperature
value measured by IR matrix sensor.
Type: WORD
Raw to engineering data:
0 .. 12000 0 .. 120.00
→
°C
4