Technical Characteristics

6.5

Control Characteristics

PID

.

Proportional Gain: 0 to 100.
Integral Time: 0.01 to 999 min/rep.
Derivative Time: 0 to 999 s.
Direct / Reverse Action.
Lower and Upper output limits.
Output rate-of-change limit: 0 to 100%/s.
Power-on safety output.
Antireset windup.
Bumpless Auto/Manual transfer.
Characterization table of the manipulated variable (MV%).

Hastelloy is a trademark of the Cabot Corp.
Monel is a trademark of International Nickel Co.
Viton and Teflon are trademarks of E. I. DuPont de Nemours & Co.
Fluorolube is a trademark of Hooker Chemical Corp.
Hart is a trademark of HART Foundation.

Summary of Contents for ld301

Page 1: ...INTELLIGENT PRESSURE TRANSMITTER WITH CONTROL CAPABILITY OPERATION AND MAINTENANCE INSTRUCTION MANUAL LD301 VERSION 6 L D 3 0 1 M E JAN 03...

Page 2: ...ch Germany Tel 49 671 794680 Fax 49 671 7946829 e mail infoservice smar de MEXICO Smar M xico Cerro de las Campanas 3 desp 119 Col San Andr s Atenco Tlalnepantla Edo Del M x C P 54040 Tel 53 78 46 00...

Page 3: ...V notch weirs in open channel flow metering TABLE the pressure signal is custom linearized according to a 16 point table enabling e g conversion of level to volume of a horizontal cylindrical tank CON...

Page 4: ...nce Instruction Manual IV NOTE This manual is compatible with version 6 XX where 6 denotes software version and XX software release The indication 6 XX means that this manual is compatible with any re...

Page 5: ...ATION CONFIGURATION 3 9 PID CONTROLLER CONFIGURATION 3 10 EQUIPMENT CONFIGURATION 3 11 EQUIPMENT MAINTENANCE 3 12 4 PROGRAMMING USING LOCAL ADJUSTMENT THE MAGNETIC TOOL 4 1 SIMPLE LOCAL ADJUST 4 2 ZER...

Page 6: ...CHARACTERISTICS FUNCTIONAL SPECIFICATIONS 6 1 CONFIGURATOR 6 3 PERFORMANCE SPECIFICATIONS 6 3 PHYSICAL SPECIFICATIONS 6 4 ORDERING CODE FOR DIFFERENTIAL MANOMETRIC AND ABSOLUTE TRANSMITTER 6 6 ORDERI...

Page 7: ...he O rings being compressed Do not use tools to close the covers Removal of the electronics cover in the field should be reduced to the minimum necessary since each time it is removed the circuits are...

Page 8: ...ting Position for LD301 Electrical Connection Mounting Bracket Adapter Allow 150mm minimum for local zero and span adjustment with magnetic tool Level Diaphragm Screws Label Level Diaphragm with exten...

Page 9: ...be rotated in order to better position the digital display To rotate it use the Housing Rotation Set Screw see Figure 1 4 WARNING EXPLOSION PROOF INSTALLATIONS The electronic housing and the sensor a...

Page 10: ...sive gases tighten the O ring until feeling the O ring touching the housing Then tighten more 1 3 turn 120 to guarantee the sealing Lock the covers using the locking screw In hazardous zones with intr...

Page 11: ...signal wiring close to power cables or switching equipment The unused outlet connection should be plugged and sealed accordingly The LD301 is protected against reverse polarity The Figure 1 6 Conduit...

Page 12: ...Connection of the LD301 working as transmitter should be done as in Figure 1 8 Connection of the LD301 working as a controller should be as indicated in Figure 1 9 Connection of the LD301 in multidrop...

Page 13: ...Fig 1 8 Wiring Diagram for the LD301 Working as a Transmitter Fig 1 9 Wiring Diagram for the LD301 Working as a Controller Optional Fig 1 10 Wiring Diagram for the LD301 in Multidrop Configuration Fig...

Page 14: ...LD301 Operation and Maintenance Instruction Manual 1 8...

Page 15: ...istance d between the plates as Where dielectric constant of the medium between the capacitor s plates Should CH and CL be considered as capacitances of flat and parallel plates with identical areas t...

Page 16: ...e for each sensor at the factory D A Converter Converts the digital data from the CPU to an analog signal with 14 bits resolution Output Controls the current in the line feeding the transmitters It ac...

Page 17: ...n the transmitter output or controller PV may have the following characteristics according to the applied pressure Linear for pressure differential pressure and level measurement Square root for flow...

Page 18: ...LD301 manual de Instru es Opera o e manuten o 2 4 Fig 2 3 LD301 Software Block Diagram...

Page 19: ...iscarded Display Can alternate between two indications as configured in DISPLAY THE DISPLAY The integral indicator is able to display one or two variables which are user selectable When two variables...

Page 20: ...PV in this case 25 00 mmH20 DISPLAY DESCRIPTION INIT The LD301 is in initializing after power on CHAR The LD301 is characterization mode See Section 3 Trim FAIL SENS Sensor failure Refer to Section 5...

Page 21: ...ugh 15 place the LD301 in the multidrop mode with current control CONTROLLER MODE The LD301 always controls the output current in accordance with the value calculated for the Controlled Variable regar...

Page 22: ...ce between the configurator and the transmitter do not interrupt the Pressure measurement and do not disturb the output signal The configurator can be connected on the same pair of wires as the 4 20 m...

Page 23: ...nknown and Special SENSOR FLUID Silicone Inert Special Unknown and None SENSOR ISOLATING DIAPHRAGM 316 SST Hastelloy C Monel Tantalum and Special SENSOR TYPE It shows the sensor type SENSOR RANGE It s...

Page 24: ...reading equal to zero must be active when the pressures of differential transmitter cameras are equalized or when a manometric transmitter opened to atmosphere or when or when the absolute transmitter...

Page 25: ...Pressure Trim is used to correct the measurement In the transmitter mode the Lower Value always corresponds to 4 mA and the Upper Value to 20 mA In the controller mode the Lower Value corresponds to...

Page 26: ...en selecting a unit make sure that it will not require readouts greater than this limit For User reference Table 3 1 presents a list of recommended sensor ranges for each available unit In application...

Page 27: ...is water at 20 C Tank volume is d 2 4 l 2 2 4 6 18 85 m 3 The wet tap shall be subtracted from the measured pressure in order to obtain the tank level Therefore a calibration without reference shall...

Page 28: ...table to compensate for example the variation of Reynolds number at the flow measurement TABLE The output is a curve formed by 16 points These points may be edited directly on the XY Table of the LD30...

Page 29: ...wing formula dt PV INCREMENT ON TOTALIZATI FLOWRATE MAXIMUM TOT The totalization method uses such totalized value and through three parameters MAXIMUM FLOWRATE TOTALIZATION INCREMENT and TOTALIZATION...

Page 30: ...flow and the minimum time allowable for the counter overrun i e the time required for the totalization to reach 99 999 999 In the example if U_TOTAL 1 the totalization increment is 1 dm 3 The time re...

Page 31: ...oint Tracking and Power On The Control Action Mode enables the selection of the desired output action direct or reverse In direct action a PV increase causes an output increase in reverse action a PV...

Page 32: ...mulated by the totalizer SP Setpoint in percentage SP Setpoint in engineering units ER Error in percentage PV SP S INDIC Used to cancel the second indication Table 3 4 Variables for Display Indication...

Page 33: ...there is the main plate change to avoid communication problems OP_COUNT Every time a change is made there is an increment in the respective change counter for each monitored variable according to the...

Page 34: ...arameters are automatically transferred The calibration parameters however remain safe in the main board so that the working range cannot be accidentally modified When the replaced part is the sensor...

Page 35: ...n mode of the magnetic switches configures the jumpers located at the top of the main circuit board as indicated in Table 4 1 SI COM OFF ON NOTE SIMPLE LOCAL ADJUST COMPLETE LOCAL ADJUST 1 Disabled Di...

Page 36: ...Adjust The LD301 works differently when a simple local adjustment is selected in the transmitter mode and in the controller mode In the transmitter mode the simple local adjustment is used for Zero an...

Page 37: ...owse the options of a branch and by placing it in S details of the chosen option are shown Figure 4 2 Programming Tree Using Local Adjustment shows the LD301 available options Fig 4 2 Local Adjustment...

Page 38: ...ERATION branch starting with function AUTO MA Auto Manual A M Z Moves to the SETPOINT INCREASE function S Toggles controller status Automatic to Manual or Manual to Automatic A and M indicate status S...

Page 39: ...ned acting on the Proportional Integral and Derivative terms and also to alter the PID mode The implemented algorithm is a PID type with the following characteristics The proportional action is given...

Page 40: ...emoved or 999 minutes are reached Z Moves to the TD_ADJUSTMENT function S Decreases the integral time until the magnetic tool is removed or 0 minutes is reached Td Adjust TD Z Moves to the DERIVATIVE...

Page 41: ...display indication The configuration options implemented in this branch are the following Selection of the variable to be shown on Display 1 and on Display 2 Working range calibration for the Transmi...

Page 42: ...LCD_2 Z Moves to the RANGE function S Starts selection of variable to be indicated as secondary display The procedure for selection is the same as for LCD_1 above DISPLAY LCD2 LCD1 DESCRIPTION SP Set...

Page 43: ...ches mercury column at 0o C ftH2O Feet water column at 20o C mmH2O millimeter water column at 20o C mmHg millimeter mercury column at 0o C psi pounds per square centimeter Bar Bar Mbar millibar g cm2...

Page 44: ...hed The span is maintained Z Moves to the SPAN ADJUST MENT function S Decreases Output in transmitter mode increases the Lower Pressure Value until the magnetic tool is removed or the maximum for the...

Page 45: ...UNIT function S Escapes to the FUNCT menu of the MAIN menu Function FUNCT Z Moves to the MODE function S Starts selection of input function After activating S you can move around the available option...

Page 46: ...ou can move around the options listed in the table below using Z T o select the desired option activate S OPERATION MODES DISPLAY DESCRIPTION XMTR Transmitter PID Controller ESC escape Table 4 6 Opera...

Page 47: ...s to the main menu PRESSURE TRIM TRIM This field of the tree is used to adjust the digital reading according to the applied pressure The pressure TRIM differs from RANGING WITH REFERENCE since the TRI...

Page 48: ...d as the Lower Pressure value corresponding to the applied pressure Z Moves on to function SAVE if the Lower Pressure Trim LOWER is running or to the Upper Pressure Trim UPPER S Adjusts the transmitte...

Page 49: ...ERO TRIM function S Escapes to the MAIN menu ESCAPE LOCAL ADJUSTMENT ESC This branch of the main tree is used to leave the Local Adjustment mode placing the Transmitter or Controller in the monitoring...

Page 50: ...LD301 Operation and Maintenance Instruction Manual 4 16...

Page 51: ...ransmitter according to the wiring diagram shown on Section 1 Figures 1 5 1 6 and 1 7 ERROR MESSAGES When communicating using the CONFIGURATOR the user will be informed about any problem found by the...

Page 52: ...entered exceeded the factory characterized value by more than 10 PASSED PARAMETER TOO LARGE Parameter above operating limits PASSED PARAMETER TOO SMALL Parameter below operating limits Table 5 1 Error...

Page 53: ...spare one Replace sensor Symptom INCORRECT OUTPUT Probable Source of Trouble Transmitter Connections Check power supply voltage Check for intermittent short circuits open circuits and grounding proble...

Page 54: ...commended The oscillating circuit is a part of the sensor and the replacement of one implies replacing the other To remove the sensor from the electronic housing the electrical connections in the fiel...

Page 55: ...Maintenance Procedure 5 5 Fig 5 1 Exploded View...

Page 56: ...Avoid bending the backup ring and inspect it for knits cuts etc Be careful when mounting it The flat side which shines more than the beveled side shall be mounted against the O ring Figure 5 3 For the...

Page 57: ...Tighten the screw 8 to lock the body to the sensor ELECTRONIC CIRCUIT Plug sensor connector and power supply connector to main board If there is a display attach it to the main board by means of 4 scr...

Page 58: ...sensor or the main board In the case of a new sensor the main board will have the most updated information in the opposite case the sensor will have the correct information Depending on the situation...

Page 59: ...BUNA N Flange VITON Flange TEFLON Flange ETHYLENE PROPYLENE Flange TEFLON spring loaded for models A5 M5 M6 H2 H3 H4 and H5 NOTE 6 Adapter BUNA N Adapter VITON Adapter TEFLON Adapter ETHYLENE PROPYLE...

Page 60: ...sia Absolute 20 8 to 2500 kPa 3 to 360 psia Absolute 0 208 to 25 MPa 30 to 3600 psia Differential High Static Pressure 0 417 to 50 kPa 1 67 to 200 inH2O Differential High Static Pressure 2 08 to 250 k...

Page 61: ...Without Adapter 1 2 14 NPT With Adapter Others Specify Process Connection High Side 1 2 3 4 6 7 8 3 150 ANSI B16 5 RF 3 300 ANSI B16 5 RF 4 150 ANSI B16 5 RF 4 300 ANSI B16 5 RF DN 80 PN 25 40 DN 100...

Page 62: ...LD301 Operation and Maintenance Instruction Manual 5 12...

Page 63: ...o 45 Vdc Load Limitation Indicator Optional 4 1 2 digit numerical and 5 character alphanumerical LCD indicator Hazardous Area Certifications Explosion proof weather proof and intrinsically safe CENELE...

Page 64: ...han 5 0 seconds after power is applied to the transmitter Volumetric Displacement Less than 0 15 cm3 0 01 in3 Overpressure and Static Pressure Limits From 3 45 kPa abs 0 5 psia to 8 MPa 1150 psi for r...

Page 65: ...6 Absolute models diaphragms in Tantalum Monel or fill fluid in Fluorolube 0 1 URL span URL 0 1 of span 0 025 URL span 0 1 URL 0 05 1 0 1 URL span of span 0 0085 URL span 0 025 URL 0 01 0 006 URL spa...

Page 66: ...request The LD301 is available in NACE MR 01 75 compliant materials Nonwetted Parts Electronic Housing Injected aluminum with polyester painting or 316 SST NEMA 4X IP67 Blank Flange Plated carbon ste...

Page 67: ...tput rate of change limit 0 to 100 s Power on safety output Antireset windup Bumpless Auto Manual transfer Characterization table of the manipulated variable MV Hastelloy is a trademark of the Cabot C...

Page 68: ...uorolube Oil 2 Tantalum and Monel diaphragm are not available for Range 1 Monel 400 Silicone Oil Tantalum Silicone Oil Tantalum Fluorolube Oil Others Specify COD Flange s Adapter s and Drain Vent Valv...

Page 69: ...dicator COD Process Connection Low Side 0 1 9 Z 1 4 18 NPT Without Adapter 1 2 14 NPT With Adapter Seal Remote Specify Others Specify COD Electrical Connections 0 A B Z 1 2 14 NPT M20 x 1 5 Pg 13 5 DI...

Page 70: ...APPENDIX A...