Section 6
6.1
TECHNICAL CHARACTERISTICS
Functional Specifications
Process Fluid
Liquid, gas or vapor.
Output Signal
Two-wire, 4-20 mA controlled according to NAMUR NE43 Specification and with superimposed
digital communication (HART Protocol). See the figure below.
Power Supply
12 to 45 Vdc.
Load Limitation
Indicator
Optional 4 1/2-digit numerical and 5-character alphanumerical LCD indicator.
Hazardous Area Certifications
Explosion proof, weather proof and intrinsically safe (CENELEC NEMKO/ATEX, BVS, CSA and
FM standards).
Zero and Span Adjustments
Noninteractive, via digital communication.
NEW
Output Current
Satured
Satured
Failure
Set Range
Pressure (%)
Failure
21.0
20.5
20.0
4.0
3.6
3.8
-1.25% 0%
-1.25%
100% 103.25%
Maximum Detected
Pressure
Minimum Detected
Pressure