LD301 – Operation and Maintenance Instruction Manual
4.6
Kp - Adjust (KP)
Z:
Moves to the PROPORTIONAL GAIN DECREASE function.
S:
Increases the proportional gain until the magnetic tool is removed or 100 is reached.
Z:
Moves to the TR_ADJUSTMENT function.
S:
Decreases the proportional gain until the magnetic tool is removed or 0.0 is reached.
Tr - Adjust (TR)
Z:
Moves to the INTEGRAL TIME DECREASE function.
S:
Increases the integral time until the magnetic tool is removed or 999 minutes are
reached.
Z:
Moves to the TD_ADJUSTMENT function.
S:
Decreases the integral time until the magnetic tool is removed or 0 minutes is
reached.
Td - Adjust (TD)
Z:
Moves to the DERIVATIVE TIME DECREASE function.
S:
Increases the derivative time until the magnetic tool is removed or 999 seconds are
reached.
Z:
Moves to the ACTION function.
S:
Decreases the derivative time until the magnetic tool is removed or 0 seconds is
reached.
Action (ACT)
Z:
Moves to the SAVE function.
S:
Toggles the action direct to reverse or reverse to direct.
The far right character of the unit/function-field indicates the present mode:
D = direct action
R = reverse action