Configuration
3.15
Figure 3.22 - Step 5 - FI302
Figure 3.23 - Step 6 - FI302
Option FEED allows the
user to correct the current
calibration. In order to
implement the correction,
read the measured current
on the miliamperimeter
and enter with this value.
This option makes it
possible to correct Lower
and Upper current
calibration points. An
arrow pointing upward
increments the current.
In order to decrement
the upper value, place
the magnetic tool in
orifice
Z
to shift the
arrow to the downward
position an then, by
inserting and keeping
the tool in orifice
S
, it is
possible to decrement
the upper value.
Place the magnetic
tool in orifice
S
to shift
the arrow to the
downward position
and decrement the
calibration current in
accordance with the
measured value. An
arrow pointing
downward decrements
the value.