FI302 - Operation and Maintenance Instruction Manual
3.14
Figure 3.19 - Step 2 - FI302
Figure 3.20 - Step 3 - FI302
Figure 3.21 - Step 4 - FI302
Insert the
magnetic tool in
orifice
S
once
more and
LOC
ADJ
should be
displayed
Remove the
magnetic tool
from orifice
S
.
This parameter is used to
calibrate the lower current
point. In order to change the
lower value, simply insert the
magnetic tool in orifice
S
as
soon as upper is shown on the
display. An arrow pointing
upward (
↑↑↑↑
) increment the
value and an arrow pointing
downward (
↓↓↓↓
) decrement the
value. Write 4.00 mA to lower
parameter. Insert the mili-
amperimeter in respective
terminal and read the
measured value to enter in
Feed parameter and correct
your desired generated
current.
Place the magnetic tool
in orifice
Z
. In case this
is the first configuration,
the option shown on the
display is the
TAG
with
its corresponding
mnemonic configured
by the SYSCON.
Otherwise, the option
shown on the display
will be the one
configured in the prior
operation. By keeping
the tool inserted in this
orifice, the local
adjustment menu will
rotate.
This parameter is used to
calibrate the upper current
point. In order to change
the upper value, simply
insert the magnetic tool in
orifice
S
as soon as upper
is shown on the display. An
arrow pointing upward (
↑↑↑↑
)
increment the value and an
arrow pointing downard (
↓↓↓↓
)
decrement the value. Write
20 mA to upper parameter.
Insert the miliamperimeter
in respective terminal and
read the measured value to
enter in Feed parameter
and correct your desired
generated current.
In order to decrement
the lower value, place
the magnetic tool in
orifice
Z
to shift the
arrow to the downward
position and then, by
inserting and keeping
the tool in orifice
S
, it is
possible to decrement
the lower value.
Summary of Contents for FI302
Page 1: ...F I 3 0 2 M E...
Page 6: ...FI302 Operation and Maintenance Instruction Manual VI...
Page 12: ...FI302 Operation and Maintenance Instruction Manual 1 6...
Page 30: ...FI302 Operation and Maintenance Instruction Manual 3 16...
Page 36: ...FI302 Operation and Maintenance Instruction Manual 4 6...
Page 39: ...Technical Characteristics 5 3...
Page 40: ...FI302 Operation and Maintenance Instruction Manual 5 4...