Configuration
3.3
It is possible to calibrate the transmitter by means of parameters CAL_POINT_LO and CAL-POINT-
HI.
Let’s take the lower value as an example: write 4 mA or the lower value in parameter
CAL_POINT_LO.
Figure 3.2 - Calibrating the Cal Point Lo – FI302
Always keep in mind that, simply by writing in this parameter, the trim procedure is initialized.
Read the current in the multimeter and write that value in parameter FEEDBACK_CAL. Write in this
parameter until it reads 4.0 mA or the lower value readout of the multimeter.
Figure 3.3 - Feedback of Current Lo Value
This parameter
indicates where the
converter should be
when the setpoint lower
value is 0%.
The desired value
should be entered.
This parameter should
be set with the actual
output current during the
calibration procedure.
The value should be
entered here.