FI302 - Operation and Maintenance Instruction Manual
3.8
Those 8 points are numbered from 1 to 8, and are contained in the CURVE_X (In Coordinates) and
CURVE_Y (Out Coordinates) parameters. CURVE_X parameter requires points in crescent order.
I.e. succeeding points be greater than preceding points, or parameter will not be accepted.
CURVE_Y parameter does not require this, so a non-monotone curve is allowed.
When writing to CURVE parameters, remember to put the point coordinates in the correct order.
Figure 3.11 - Configuring the Characterization Curve - X points
Figure 3.12 - Configuring the Characterization Curve - Y points
Via Local Adjustment
The
FI302
has 3 output transducers and its device leaves SMAR with factory settings. The factory
setting establishes only the transducers #1 as default for local adjustment. In order to configure the
others via local adjustment, the user should configure them in the display transducer via SYSCON,
according specific instructions for this transducer block.
In order to enter the local adjustment mode, place the magnetic tool in orifice “Z” until flag “MD”
lights up in the display. Remove the magnetic tool from “Z” and place it in orifice “S”. Remove and
reinsert the magnetic tool in “S” until the message “
Loc-Adj
” is displayed. The message will be
This parameter
defines the
coordinates X
The values should be
configured in crescent
order.
FI2EM312.CDR
This parameter
defines the
coordinates Y
It is not necessary
to follow any order.
A monotone curve
is allowed.
Summary of Contents for FI302
Page 1: ...F I 3 0 2 M E...
Page 6: ...FI302 Operation and Maintenance Instruction Manual VI...
Page 12: ...FI302 Operation and Maintenance Instruction Manual 1 6...
Page 30: ...FI302 Operation and Maintenance Instruction Manual 3 16...
Page 36: ...FI302 Operation and Maintenance Instruction Manual 4 6...
Page 39: ...Technical Characteristics 5 3...
Page 40: ...FI302 Operation and Maintenance Instruction Manual 5 4...