FI302 - Operation and Maintenance Instruction Manual
3.4
In order to end the trim procedure, choice DISABLE in the parameter CAL_CONTROL
.
Figure 3.4 - Closing the Calibration Lo Procedure
Let’s take the upper value as an example:
Write 20 mA in parameter CAL_POINT_HI. Always keep in mind that, simply by writing in this
parameter, the trim procedure is initialized.
Figure 3.5 - Calibrating the Cal Point Hi – FI302
This parameter ends
the calibration
procedure.
The enable option indicates
that the calibration process
is being done. In order to
finalize its procedure, the
user should set it to
disable.
This parameter
indicates where the
converter should be
when the setpoint is
100%.
The desired value
should be entered.