7 Commissioning
SMA Solar Technology AG
Operating manual
SI44M-80H-13-BE-en-15
78
• Increased self-consumption range (SlfCsmp)
You determine the percentage of the battery capacity that is to be used for increased self-consumption on the
shortest day of the year.
• Range for battery-backup function (BURes)
You specify the percentage of the battery capacity that is to be used for the battery-backup function on the longest
day.
The longer the days become, the more the SlfCsmp range automatically increases and the BURes range decreases.
The range for increased self-consumption reaches its maximum on the longest day. This results in the seasonal
progression of the ranges.
t
SOC
0 %
100 %
A
B
C
D
E
Winter
Summer
Winter
Figure 18: Ranges of the battery state of charge as a function of the season for the northern hemisphere (example)
Range
Explanation of the range and parameters
Behavior of the Sunny Island inverter
A
Self-consumption range (SlfCsmp)
11)
The
SlfCsmp
range applies to the shortest day of the
SlfCsmp
range is used and the
BURes
range in-
creased accordingly.
The Sunny Island uses the battery for in-
creased self-consumption.
Battery > Ranges of application > Minimum width
of backup power range
11)
This range can be adjusted for all battery types.