14 Troubleshooting
SMA Solar Technology AG
Operating manual
151
SI44M-80H-13-BE-en-15
Event number
Message, cause and corrective measures
6614
Overload
The device at Lxx has been loaded over its 5-minute rated capacity.
Corrective measures:
• Reduce the power of the loads.
6615
Overload
The device at Lxx has been loaded over its 30-minute rated capacity.
Corrective measures:
• Reduce the power of the loads.
6616
Overload
The device at Lxx has been loaded over its rated short-term capacity.
Corrective measures:
• Reduce the power of the loads.
7002
7003
7004
Fan sensor error permanently on
There is a short circuit or cable break at a temperature sensor of the device at line conductor
Lxx.
Corrective measures:
• Contact the Service.
7010
Short circuit battery temp. sensor > Check sensor status and function
Short circuit on battery temperature sensor
Corrective measures:
• Ensure that the battery temperature sensor is correctly connected.
• Contact the Service.
7011
Cable break battery temp. sensor > Check sensor status and function
Cable break, battery temperature sensor
Corrective measures:
• Ensure that the battery temperature sensor is correctly connected.
• Contact the Service.
7101
SD memory card defective
Micro SD card in the inverter is faulty.
Corrective measures:
• Replace the micro SD card.