10 Disconnecting the Inverter from Voltage Sources
SMA Solar Technology AG
66
STP5-9TL-IA-en-10
Installation Manual
5. Release and remove all DC connectors. To do this,
insert a slotted screwdriver (blade width: 3.5 mm)
into one of the side slots and pull the DC connectors
straight out. Do
NOT PULL ON THE CABLE
.
7. Ensure that no voltage is present at the DC inputs of
the inverter.
8. Loosen all screws of the enclosure lid using an
Allen key (AF 5) and remove the enclosure lid.
6.
Danger to life due to high voltages
The capacitors in the inverter take five minutes to discharge.
• Wait five minutes before opening the enclosure lid.