7 Commissioning
Installation Manual
SB3-5TLUS22-IA-en-10
57
7.3 Changing the Country Data Set using a Communication Product
By default, the inverter is set to a specific country data set. You can see which country data set was
set as default at the factory on the type label and the supplementary sheet provided with the default
setting. If the inverter's default country data set does not apply to your country or you want to use the
inverter in a backup or off-grid system, then you must change the country data set.
Requirements:
☐ A communication product that is appropriate for the type of communication used must be
available.
☐ The responsible grid operator must approve changes of grid-relevant parameters.
☐ An SMA Grid Guard code for changing the grid-relevant parameters must be available
(for application for the SMA Grid Guard code, see certificate "Application for a Personal
Access Code" at www.SMA-Solar.com).
1. Access the user interface of the communication product.
2. Enter the SMA Grid Guard code.
3. Select the
CntrySet
or
Set country standard
parameter and set the required country data set.
4. Save setting.