35
5.2
Summary of available equipment
5.2.1
Battery test
The battery presence test is performed in the following manner: every 30 seconds for the first 20 minutes after
commissioning and every 15 minutes after. As soon as a fault is detected, the test is performed every 30 seconds
until 20 minutes after the fault disappears.
The impedance measurement test occurs every 4 hours if the mains is present on the power supply and if his
current is < 12A. The impedance limit value is 16m
10 %
in 24V and 32m
10%
in 48V if the jumper is set on '75',
and becomes 24m
10%
in 24V and 48m
10%
for 48V if the jumper is set on '50' (see chapter 1.2.5).
5.2.2
Temperature compensation:
A battery voltage compensation system maintains the charge characteristics within the limits specified by the
battery manufacturer across the entire operational temperature range.
5.2.3
Battery low voltage protection:
-
The battery low voltage protection threshold is 21,6 V
±3 %
(SON 24V 12A MS150 RACK) or 43.2 V
±3 %
(SON
48V 12A MS150 RACK).
-
The element causing the cut-out will be in the + position.
5.2.4
Battery reverse connection protection
-
At start-up : the battery relays will not close
-
During operation : the fuse F8 will blow out
6
Maintenance
In order to ensure maximal and durable service, we strongly recommend that your product be maintained clean and
ensure that it is installed in a dry and ventilated location. We shall in no case be liable for damages associated with
improper use or incorrect maintenance of the equipment.
Replacing the original battery with a battery of incorrect type may result in an explosion hazard.
Used batteries must be disposed of in compliance with recycling requirements.
7
Fuse protections
F1 mother board (mains):
Rating
– type – size – breaking capacity
6.3 A T for 24V version
8A T for 48V version
5x20
1500 A breaking capacity
F8 mother board
Rating
– type – size
12,5A T
5x20
F1 to F6 main outputs board (6 outputs) :
rating - type
– size
32 A gG
10x38
Faux1 to Faux3 auxiliary outputs board (3 outputs):
rating - type
– size
5A F
5x20
External battery fuse (not fitted with PSE)
rating - type
[Ibmax (mains not present)] A
gG type