Troubleshooting procedure
The indicator light are not illuminated
•
Check the mains voltage
•
Check the primary fuse F1 on the power and control board
•
Check that the flat ribbon cable is correctly connected
The output indicator light is yellow
•
Check the output fuses F1 to F6
•
Check the auxiliary fuses F1 to F3
The battery indicator light is yellow
•
Check that the nominal battery voltage is ok with the sytem voltage
•
Check the polarity connections of each battery and on the rack battery connector
•
Check the battery connections and the battery fuse connections
•
Check the voltage of each battery block (>1,9V / >5,7V / >10,8V)
•
Check that the battery is approuved (see Pr 1.2.5)
•
If the mains is present, check that the output current is <12A
•
The internal battery resistor may be too high: replace the battery
The mains indicator light is yellow
•
Check the mains voltage
•
Check the primary fuse F1 on the power and control board
•
Check that cooling of the rack is sufficient and that the ambient temperature is < 45°C