Lynx Model LX-85A
9
LYNX MODEL LX-85A NON-DIRECT VENT, SIDEWALL VENTING
ALL JOINTS MUST BE LIQUID AND PRESSURE TIGHT. USE 76 mm (3”) DIA. PVC/CPVC SCHEDULE 40 PIPE FOR AIR
INTAKE OR U/L LISTED SINGLE WALL 76 mm (3”) DIA. AL129-4C STAINLESS STEEL VENTING MATERIAL (see page 6) OR
CERTIFIED PVC OR CPVC VENTING CERTIFIED TO THE STANDARD FOR TYPE BH GAS VENTING SYSTEMS, ULC S636.
Figure 7. Non-direct vent, side wall venting - utilizing Certified PVC or CPVC Venting pipe for venting.
Figure 8. Non-direct vent, side wall venting - utilizing stainless steel vent materials for venting.
* AL 29-4C IS A REGISTERED TRADEMARK OF ALLEGHENY LUDLUM CORP.
** Definition of Snow Line: Knowledge of local conditions will reveal the maximum height that repeated snowfalls accumulate to.
The height should be used as the SNOW LINE.
SLOPE UP 20mm/m
(1/4" PER FOOT) MIN. FROM
BOILER TO VENT
TERMINATION
152mm (6") MIN.
229mm (9") MAX.
TERMINATION 90° ELBOW
WITH SCREEN
305mm (12") MIN.
76mm (3") DIA.
CERTIFIED PVC OR
CPVC VENTING PIPE
FOR VENT
SLOPE UP 20mm/m
(1/4" PER FOOT) MIN. FROM
BOILER TO VENT
TERMINATION
152mm (6") MIN.
229mm (9") MAX.
305mm
(12") MIN.
A U/L LISTED WALL THIMBLE
MUST BE USED ON
COMBUSIBLE WALLS. S/F
P/N 440695 (ADJUSTIBLE
127mm TO 203mm [5" TO 8"])
MAY BE USED. ABOVE
THIMBLE MUST BE USED
WITH HEAT-FAB SLIP JOINT
CONNECTOR
76mm (3") DIA.
AL29-4C STAINLESS
STEEL MATERIAL
STANDARD 90°
ELBOW