Lynx Model LX-85A
32
MODE
DISPLAY
DESCRIPTION & TEMPERATURE DISPLAY
Space heating supply water temperature could be changed by pressing
“Up/Down” button. Settable from 32°–85°C (90°–185°F)
(steps of 1 F). The default value is 80°C (176°F).
Press “Enter” button to store.
(see note 1)
Domestic hot water supply temperature could be changed by
pressing”Up/Down” button. Settable from 40°–85°C (104°–185°F)
(steps of 1 F). The default value is 80°C (176°F)
Press “Enter” button to store.
(see note 2)
Domestic hot water tank temperature could be changed by
pressing “Up/Down” button. Settable from 32°–71°C (90°–160°F)
(steps of 1 F). The default value is 60°C (140°F).
Press “Enter” button to store.
(see note 3)
Temperature display shows actual supply water temperature.
Temperature display shows actual return water temperature.
Temperature display shows actual DHW tank temperature.
(if the water tank is equipped with sensor).
Temperature display shows actual flue gas temperature.
Temperature display shows actual outside temperature.
(if outdoor sensor is used)
NOTE:
1-
For space heating mode “0” (boilers not utilizing outdoor sensor))
2-
For DHW mode “2” (storage tank with Aquastat)
3-
For DHW mode “1” (storage tank with sensor)
Table 4
VIEWING AND CHANGING TEMPERATURES
Press “SELECT” button for viewing different modes on “MODE DISPLAY”
blinking
blinking
blinking