background image

6

INTREPID TRDV

OIL SUPPLY PIPING

Install the oil tank or tanks and piping from tank to burner.  Follow local

codes and practices, NFPA No. 31, INSTALLATION OF OIL BURNING

EQUIPMENT and the instruction sheet attached to the oil burner pump.

A one-pipe system should be used for gravity fed fuel systems and for lift

systems, where the total lift is less than 8 ft. Where the total lift is greater

than 8 ft., a two-pipe system must be used.  In some instances, local

codes may require a two-pipe system for below grade fuel oil tanks.  Be

sure to set-up the fuel oil pump for the piping system used; follow the

instructions attached to the pump.  Be sure to include a good quality, low

pressure drop fuel oil filter in the supply line from the tank.  This is nec-

essary, especially at low fuel oil flow rates (small nozzle sizes), to pre-

vent nozzle plugging.  See Slant/Fin publication on one-pipe and two-

pipe fuel oil systems.

WIRING THE BOILER

• The wiring diagrams for the burner and boiler may be found on

pages 6-7.

• 24 volt control wiring should be approved Safety Circuit wire, protected 

as needed.

• Power supply wiring to the burner must be 14 gauge or heavier, as 

required, and should have a properly fused disconnect switch. 120 volt 

wiring to pumps and safety  controls must also be 14 gauge or heavier.

Wire must be enclosed in approved conduit.

•  All wiring must be installed in compliance with the National Electric 

Code, or any local or insurance codes having jurisdiction.

PRECAUTIONS BEFORE STARTING OIL BURNER

Make a positive check of A through F before starting burner:

A. Boiler and system are full of water. All air is vented from system. See 

below.

B. All wiring is completed. See pages 6-7.

C. Oil supply is connected to the burner; nozzle is installed correctly; oil 

valve is open at tank.

D. All combustible materials are cleared away.

E. All vent piping is properly installed and sealed.

F.

Burner settings are adjusted as per pages 8-11 and as shown on 

boiler jacket label.

CAUTION:

DO NOT START THE BURNER UNLESS ALL CLEANOUT

DOORS ARE SECURED IN PLACE

STARTUP 

(COMBUSTION TEST INSTRUMENTS MUST BE USED)

A. Make sure the boiler is installed and wired properly and is full of 

water.

Start the oil burner (see burner instructions for bleeding air from oil, 

etc.) IMMEDIATELY, set burner air bands to obtain a bright fire with

out smoke or oil stain.

All readings MUST be taken at the test port in the flue adapter.

See Figure 6 for test port location.

Smoke reading should be a trace or less on the smoke paper. Adjust 

the burner as necessary for proper operation.

CLEANING AND FILLING A NEW WATER BOILER

I.   BEFORE FILLING WATER BOILER

A.

Check burner to be certain it is ready for firing. DO NOT FIRE 

into an empty boiler.

B.

Be prepared to heat raw water to at least 180°F. as soon as it is 

introduced into the boiler. This procedure will remove dissolved, 

corrosive gases.

C.

Provide drain line, with valve, from boiler. Use a bottom tapping. 

Line and drain must be suitable for handling caustic solution.

II.  CLEANING WATER BOILER SYSTEM

A.

Prepare a boil-out solution of 

sodium hydroxide

(caustic soda) or

tri-sodium phosphate.

NOTE: Use caution in handling chemicals. Caustic soda is 

harmful to skin, eyes and clothing.

1.

Proportions: 1 lb. of either chemical per 50 gallons of sys-

tem water.

2.

Stir chemical in water until dissolved and pour into the boiler

through a top tapping. Replace plug.

B.

Fill the entire system with water.

C.

Start the burner, using the start-up procedure.

D.

Circulate the water through the entire system.

E.

Vent the system, including the radiation.

F.

Allow boiler water to reach operating temperature, if possible.

G.

Continue to circulate the water for a few hours.

H.

Shut off the burner.

I.

With CAUTION, drain the boiler solution to a safe location. DO 

NOT LEAVE SOLUTION SITTING IN SYSTEM OVER 2 

HOURS.

J.

Wash the water side of the boiler thoroughly using a high pres-

sure water stream. Fill and drain the boiler several times.

III. TREATING WATER FOR CORROSION CONTROL 

(This is not scale control)

A.

Prepare a solution of 

sodium chromate

.

Proportions: 6 oz. per 50 gallons of system water.

B.

Stir chemical into water until dissolved and pour into the boiler 

through a top tapping. Replace plug.

IV. FILLING AND VENTING THE WATER BOILER

A.

Refill the system with fresh water.

B.

Bring water temperature to at least 180° F. promptly.

C. Circulate water through entire system.

D.

Vent the system, including the radiation.

E.

The boiler is now ready to be put into service or on standby.

F.

If brand-name air-control devices are used, venting instructions 

furnished with the devices should be followed.

V. SAFETY CHECK FOR CONTROL SYSTEM

High limit control test:  Set thermostat high enough for boiler water 

temperature to reach high limit control setting.  When this tempera-

ture is reached, the high limit switch should open, and the burner 

should shut off automatically.  If the high limit does not operate to 

shut off the burner, the high limit or the wiring is faulty.  Repair or 

replace immediately.

Wiring to the boiler must come through an emergency power isolation

switch with a clearly marked red switch plate. This switch should be

located so that it is apparent to the homeowner when entering the base-

ment or other boiler area. The homeowner should be made familiar with

operating the toggle to provide or stop the power to the boiler.

Note: The draft is not adjustable.

The draft should not exceed 0.35”WC

during burner operation

THE FLUE IS UNDER POSITIVE PRESSURE DURING

OPERATION. ALL VENTING MUST BE SEALED AND

CHECKED ON A REGULAR INTERVAL.

OPERATING INSTRUCTIONS

Summary of Contents for INTREPID TRDV Series

Page 1: ...In addition where required by the authority having jurisdiction the installation must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically...

Page 2: ...ted within the area to be heated the boiler may be selected on the basis of gross D O E capacity output The net AHRI output ratings shown are based on an allowance for piping and pickup of 1 15 water...

Page 3: ...ion should not be mounted directly above or within 3 ft horizontally from an oil tank vent VENT PIPING A The vent piping minimum bend radius is 12 B Place metal strapping every 36 to support vent pipe...

Page 4: ...4 INTREPID TRDV...

Page 5: ...ansion tank and air scoop should be located near the pump suction See Figure 4 Alternate Pump Location PIPING TANKLESS HEATER if used I Heater capacities are listed on page 2 II Pipe the built in tank...

Page 6: ...DO NOT FIRE into an empty boiler B Be prepared to heat raw water to at least 180 F as soon as it is introduced into the boiler This procedure will remove dissolved corrosive gases C Provide drain line...

Page 7: ...INTREPID TRDV 7 SEE Adjusting Settings Error Codes for L7224C L7248L on page 8 See page 8 for other Primaries...

Page 8: ...everting to default settings or has stopped running the Outdoor Reset algorithms The warnings are cleared when the issue s is resolved b To clear Err 8 condition depress and hold all three user keys s...

Page 9: ...INTREPID TRDV 9 Basic Module Wiring less circulator...

Page 10: ...nto Combustion Chamber TURBULATOR SETTING 1 Loosen nut 1 then turn the screw 2 until the index marker 3 is aligned with the correct index number 2 Retighten the retaining nut 1 The numbers on the cast...

Page 11: ...lockwise indicator to increase combustion air turn the screw clockwise indicator to decrease combustion air 3 The final position of the air damper will vary on each installation Use instruments to est...

Page 12: ...kwise the burner head will move inside the blast tube AWAY from the end cone This achieves lower firing rates Similarly by turning the head adjustment screw counter clock wise the burner head will mov...

Page 13: ...with neutral mineral oil 9 Close main cast iron burner door door on which burner is mounted Make sure that the entire seal fiberglass rope is making good contact with the boiler casting when replacin...

Page 14: ...14 INTREPID TRDV Notes...

Page 15: ...INTREPID TRDV 15 Notes...

Page 16: ...SLANT FIN CORPORATION Greenvale N Y 11548 Phone 516 484 2600 FAX 516 484 5921 Canada Slant Fin LTD LTEE Mississauga Ontario www slantfin com Copyright 2011...

Reviews: