FACTORY parameters query and setting (table 4)
Code
Meaning
Setting range
Factory
setting
Remarks
H2
Ambient air temperature below
which heat pump will stop
working to protect
-30
℃
~
0
℃
-10
℃
H3
Defrost period setting
20min
~
90min
55min
H4
Air HE lowest tube temp below
which system will enter defrost
-15
℃
~
-1
℃
-3
℃
H5
Longest defrosting time setting
5min
~
20min 8min
H6
Air HE lowest tube temp above
which system will quit defrost
1
℃
~
40
℃
13
℃
H7
The temp difference between
ambient temp and air HE lowest
tube temp higher than which
system will enter defrost
0
℃
~
+15
℃
2
℃
H8
Ambient temp below which
system will enter defrost
0
~
20
℃
10
℃
P1
Action period setting of electric
expansion valve
20s
~
90s
30s
P2
Target superheat temp setting
-5
℃
~
10
℃
4
℃
P3
Outlet gas temp at which EEV
will adjust to keep the temp
80
℃
~
110
℃
95
℃
P4
EEV open degree when
defrosting
2
~
50
50
P5
Min open degree of EEV
2
~
30
12
P6
EEV choice for automatically and
manually
0
(
manual
)
\1
(
auto
)
1
P7
EEV step by manual
2
~
45
35
F1
Upper limit of water tank temp
setting
30
℃
~
90
℃
60
℃
F2
Circulating water pump choice
when only electric heater
working
0/1
1
0
:
work/1
:
not work
F3
Temp difference of displaying
temp and real temp of water tank
-5
℃
~
15
℃
2
℃
F4
Water flow switch installing way
choice
0 /1
0
0:independent/1
:
share
F5
Water pump working state when
heat pump standby
0/1
1
0: non-stop
1: stop
F6
Outlet water temp too high
protection at heating mode
35
℃
~
85
℃
62
℃
F7
Reserved
F8
Outlet gas temp setting for too
high protection
100
P
~
126
℃
115
P
Remarks: F4 only valid for cascade connection way.
Summary of Contents for SX-20BZA
Page 3: ......
Page 4: ......
Page 9: ...Buffertanks Skyline Energy 200Lt 3 zone buffertank dimensions April 2019...
Page 10: ...Buffertanks continued Skyline Energy 200Lt 2 zone buffertank dimensions April 2019...
Page 11: ...Buffertanks continued Skyline Energy 100Lt 2 zone buffertank dimensions April 2019...
Page 13: ......
Page 14: ......
Page 19: ...Typical installation diagram...
Page 23: ...Skyline Energy 200Lt buffertank Stainless Steel 2 zone or 3 zone...
Page 24: ...Typical 200Lt 2 zone buffertank installation...
Page 25: ...Typical V model heatpump installation...
Page 27: ...Typical V model heatpump installation Typical V model heatpump installation...
Page 29: ...Part 1 Operating panel introduction 1 Display interface 2 Buttons function Clock M power...