Onsite-testing heatpump output - continued:
Formula to Calculate Kilojoules;
4816 x LOAD x RISE / 1000/60/TIME =
kW OUTPUT
LOAD = Tank capacity plus plumbing
TIME = Duration of test
RISE = 10C
4186 x 210 x10/1000 = 8790kj
EXAMPLE:
200Lt buff10Lt plumbing,
LOAD = 210
Temperature rise was 10C,
RISE= 10
4186 x 210 x10/1000 = 8790kj
Conversion kj to kW;
Stopwatch says it took 15 minutes,
TIME= 15
8790/60/15 =
9.77kW output