DOL 278T
Technical Manual
21
6 Testing
6.1 Lamp indications
Flashing sequence
Cause
2 sec. - endless
Outdoor temperature compensation active:
Switches on in the relevant side(s) (yellow).
0.1 sec./1 sec. - 3 sec.
Misplaced outside sensor:
Move the outside sensor away from the sunlight.
Flashes in both sides (yellow).
0.1 sec./1 sec.
Short-circuited or disconnected outdoor tempera-
ture sensor:
Flashes in both sides (yellow).
1 sec./1 sec.
Blocked by falling inside temperature:
Flashes on the relevant side(s) (yellow).
0.1 sec./1 sec.
Short-circuited or disconnected indoor temperature
sensor:
Flashes on in the relevant side(s) (red).
2 sec. - endless
Emergency opening:
Switches on in the relevant side(s) (red).
As long as the emergency opening is active.
2- 80 sec.
Opens:
Switches on in the relevant side(s) (green).
While motor is opening.
0.1 sec./0.5 sec.
Power-ON indication NORM / WARM setting:
Flashing (green) Power-ON = NORM = Normal cold cli-
mate.
Flashing (red) Power-ON = WARM = Combi-Tunnel
warm climate.
5- 10 sec.
1 sec./1 sec.
Phase break/mains failure 115/230 V:
The relevant battery lamp is flashing (green, yellow or
red) after 5-10 sec.
Both emergency opening lamps switches on (red).
0.5 sec./0.5 sec.
0.5 sec./0.5 sec.
3 min.
3 min.
Maintain emergency opening for 3 minutes
After phase break/power failure has been restored
(when outside temp. is < 20’C).
In the meantime emergency opening lamps lit (red).
The relevant battery lamp is flashing (green, yellow or
red).
Opening lamps are flashing on both sides (green).