7.3 ECT/DCT 632-6
409143
ECT 632-6
409146
ECT 632-6 CSA
409144
DCT 632-6
Electrical
Rated voltage
V AC
1x230 ± 10%
3x400 ± 10%
Operating voltage
V AC
207 – 253
360 – 440
Frequency
Hz
50
60
50
Max. power consumption
At 230 V AC
A
2.2
3.0
-
Max. power consumption
At 400 V AC
-
-
1.25
Max. input power (P1)
W
473
740
483
Max. power (P2) shaft
W
-
-
-
Efficiency motor [η]
%
-
-
-
CosPhi [Φ]
Factor
-
-
-
Regulation ability
Use sinus filter in connection with frequency converter
Motor protection
Termistor
Mechanical
Cable length
mm
1350
1150
Min. duct diameter
mm
636
The diameter of the fan
blade
mm
627
Number of fan blades
pcs.
5
Fan blade pitch
°
R2
Fan output
Revolutions (rated current)
per minute
RPM
890
1040
930
Air output at 0 Pa
m
3
/h
13100
15500
13700
Air output at -10 Pa
m
3
/h
12700
14900
13100
Air output at -20 Pa
m
3
/h
12200
14500
12700
Air output at -30 Pa
m
3
/h
11700
13900
12100
Air output at -40 Pa
m
3
/h
10800
13400
11500
Air output at -50 Pa
m
3
/h
9800
12500
10500
Air output at -60 Pa
m
3
/h
-
11800
-
Power consumption at -10
Pa
W
436
692
442
Specific output at -10 Pa
m
3
/kWh
29100
21500
29600
Specific energy at -10 Pa
Watt/1000
m
3
/h
34
47
34
Testing body
AMCA Standard 210 ISO 13347 Part 3 (Ziehl-Abegg)