DA 600 LPC • DA 600 • ECT 632-6 • DCT 632-6
54
Technical User Guide
7 Technical data
7.1 DA 600 LPC
445070/445073
DA 600 LPC-11-2
445072/445075
DA 600 LPC-13-2
Electrical
Rated voltage
V AC
230 ± 10 %
Operating voltage
V AC
175 – 280
For supply voltages below the rated voltage range, a reduction of the
fan’s RPM may occur depending on the load and ambient tempera-
ture.
RCD
To be installed in accordance with applicable laws and standards.
RCD 300 mA (type B) may be used in front of the supply voltage for
LPC regulated fans.
Frequency
Hz
50/60
Leakage current to ground
mA
Max. 3
Pay attention to other leakage current sources in the house.
Max. ballast fuse
A
16
Max. power consumption
At 230 V AC supply
A
2.58
4.14
Max. input power (P1)
W
587
954
CosPhi [Φ]
Factor
0.99
Regulation ability
20 to 100% / 8 - 0 V
Motor protection
Built-in current limiter in LPC motor control.
Use fuse in front of LPC motor control.
Thermal cutout (PTO)
445070, 445071, 445072
-
Thermal cutout (PTO)
445073, 445074, 445075
Thermik S01.120.05 Separate cable
Interface
Inputs
A1: Analog fan speed
V DC
10 – 0 (default)
D1: Start / Stop
V DC
0 / 24 with internal pull-up
D2: Polarity analog input
0-10 V / 10-0 V
V DC
0 / 24 with internal pull-up
LPC-2 relay module (op-
tional)
D3: Input reversing
V DC
0 - 24 with internal pull-up
Output alarm relay
1 A, 30 V DC, 24 V AC
Mechanical
Cable length
m
2 shielded
Min. duct diameter
mm
636
The diameter of the fan
blade
mm
625
Number of fan blades
pcs.
3
Fan blade pitch
°
Periferi 25 / Nav 45