Document NO.: RD-690-39-001 Version: A Date
:
2017.12.30
4.3.10.5
Restore Factory Settings (Menu Item 7-3-5)
4.3.10.5.1 Description
The factory default settings can be restored, erasing all configuration data. Restoring to default settings will also erase
any settings pre-configured during the equipment manufacture. The equipment will default to Installation mode.
Restoring to default settings is only available at Engineer Level.
4.3.10.5.2 Operation
Please contact Siterwell Customer Service.
4.3.10.6
Communication (Menu Item 7-3-6)
4.3.10.6.1 USB communication
4.3.10.6.1.1
Description
The status of USB communication can be configured to DISABLED or ENABLED. Configuration data may be
transferred between an external device (such as a PC) and the control and indicating equipment by USB port. The
external device needs to be running Siterwell Software.
The default status of USB communication is DISABLED.
Disabled USB will be indicated on the LCD and can be reviewed using
【
DISABLED
】
key.
4.3.10.6.1.2
Operation
1)
By pressing the
【
1
】
key from the Commun screen enters into USB mode.
2)
Press the
【
UP
】
and
【
DOWN
】
key to select the status DISABLED or ENABLED.
3)
Press
【
ENTER
】
key to confirm the selection and it will automatically return to previous menu.
4.3.10.6.2 RS485 communication
4.3.10.6.2.1
Description
The status of RS485 communication can be configured to DISABLED or ENABLED. Main Panel ID number can be
set from 01 to 32. Maximum up to 32 Main Panels can make a network group by RS485 port.
The default status of RS485 communication is DISABLED.
Disabled RS485 will be indicated on the LCD and can be reviewed using
【
DISABLED
】
key.
4.3.10.6.2.2
Operation
1)
By pressing the
【
2
】
key from the Commun screen enters into RS485 mode.
2)
Press the direction keys to select the status DISABLED or ENABLED or Main Panel ID number.
3)
Press
【
ENTER
】
key to confirm the selection and it will automatically return to previous menu.
4.3.10.6.3
4.3.10.6.3.1
Description
The status of ETHERNET communication can be configured to DISABLED or ENABLED. Once setting the
ENABLED, it will enter into the configuration of Router IP Address, IPV4 Address, Mask Address and Port number.
DD/MM/YY <Panel Status> HH:MM:SS
1. USB
2. RS485
3. Ethernet [Common]
Summary of Contents for GS690
Page 18: ...18 Document NO RD 690 39 001 Version A Date 2017 12 30 Figure 11 Figure 12 ...
Page 27: ...27 Document NO RD 690 39 001 Version A Date 2017 12 30 ...
Page 29: ...29 Document NO RD 690 39 001 Version A Date 2017 12 30 ...
Page 30: ...30 Document NO RD 690 39 001 Version A Date 2017 12 30 ...
Page 31: ...31 Document NO RD 690 39 001 Version A Date 2017 12 30 ...