Document NO.: RD-690-39-001 Version: A Date
:
2017.12.30
3.5
Panel Wiring
Warning
:
When connecting wires, please operate without power.
3.5.1 Primary Power source (AC) and Earth Ground Connections
AC Power connections are made inside the control panel cabinet. The Primary source for the GS690 is 120/220 VAC,
60/50Hz, 4 Amps. Run a pair of wires with Earth conductor from the protected premises main breaker box to connector
(AC Terminal) of the power supply board. As per National Electrical Code, use 12 AWG (2.00 mm
2
) or heavier gauge
wire with 600V insulation. No other equipment shall be connected to this circuit. In addition, this circuit must be provided
with over current protection and may not contain any power disconnect devices. A separate Earth Ground connection
must be made to ensure the proper panel operation and lighting and transient protection. Connect the Earth Ground wire
(Min. 12AWG / 2.00 mm
2
).
Figure
–17
3.5.2 Standby Power Source (Batteries)
Observe polarity when connecting the battery. Connect the battery cable to connector CN13 on the Zone board using the
connector and cable provided. The battery charger is current
– limited and capable of recharging sealed lead acid type
batteries up to 12Ah.
Figure
–18
Summary of Contents for GS690
Page 18: ...18 Document NO RD 690 39 001 Version A Date 2017 12 30 Figure 11 Figure 12 ...
Page 27: ...27 Document NO RD 690 39 001 Version A Date 2017 12 30 ...
Page 29: ...29 Document NO RD 690 39 001 Version A Date 2017 12 30 ...
Page 30: ...30 Document NO RD 690 39 001 Version A Date 2017 12 30 ...
Page 31: ...31 Document NO RD 690 39 001 Version A Date 2017 12 30 ...