Fault found 

Possible cause 

Action to take 

Rated voltage is wrong 

Rated voltage of unit and on-board circuit must be 
the same. Order new unit. 

Air nozzles closed or 
covered 

Open nozzles or free up inlet/outlet openings. 

Electrical wires are 
underdimensioned 

Install recommended cable cross-section. 

Blower only operate at 
reduced power 
 

Heat exchanger severely 
contaminated 

Carefully clean avoiding damage which can lead to 
leaks. WARNING! Observe safety instructions. 

Vehicle engine is not 
running 

Start engine. 

Cooling water still cold 

Wait until the engine reaches operating temperature 

Water valve closed 

Open valve. See the vehicle manufacturer’s operating 
instructions. 

Water lines kinked or 
squashed 

Eliminate fault by installing correctly. 

Heating doesn’t function 

Water pump pressure 
insufficient 

Heat exchanger does not have cooling water flowing 
through. Install additional pump or more powerful 
one. 

Volumetric air flow from 
blower is too low 

See action to take under “Blower” 

Open valve to the maximum. 

Water flow rate through 
heat exchanger is too 
low 

Water lines kinked or squashed. Relay hoses. Water 
pump pressure too low (see above for action). 
Flush-out water circuit. 

Air in heat exchanger 

When the pumping pressure is sufficient the heater is 
self bleeding. Install additional or more powerful 
water pump. 

Unit is underdimensioned  Install a more powerful unit. 
Insufficient pumped 
water pressure 

Install additional pump or a more powerful one. 

Reduced heating 
performance 

Heat exchanger severely 
contaminated 

Carefully clean avoiding damage which can lead to 
leaks. 

 Products 

which

 have already been pulling appart are not covered by guaratee.

 

 

5 - Security advice 

 

Consider the following advice for your own safety : 
 

 

Installation must only be done by well-formed and authorized specialists. 

 

Product must operate on a well-ventilated place. 

 

Products  have  to  be  used  only  according  to  the  intended  use.  Products  shall  not  used  in 

improper environment. Pay attention to guarantee. 

 

Before using products, ensure that regulations and laws are strictly adhered according to the 

country. 

 

For  security  reasons  (fire  hazards),  fuses  with  required  amperage  must  be  used  to  protect 

electrical connections. 

 

Cut electrical connections before working on product. 

 

Do not get into contact with the heat exchanger and its connections. 

 

Do not grip into the unit and do not put objects inside. 

 

 

Summary of Contents for ARIZONA

Page 1: ... Ind B Page 1 of 6 ARIZONA 1 Device description 2 Operation 3 Mounting information 4 Trouble shooting 5 Security advice SIROCO S A S 10 rue Jean Rostand Z I BP 315 69745 GENAS Cedex Tel 33 0 4 78 90 96 96 Fax 33 0 4 78 90 15 98 www siroco fr ...

Page 2: ...knob ARIZONA s front plate is available in different colors white grey anthracite or black Heater can be equipped with 600 400 or 300 blower that supplied in 12 V or 24 V with connections pipes diameters of 16 mm Product part numbers ARIZONA 600 ARIZONA 400 ARIZONA 300 Voltage Front plate color Part number Part number Part number White 0120 0001 0120 0101 0120 0201 Grey 0120 0002 0120 0102 0120 02...

Page 3: ...d anticorrosive for copper and aluminum Use a cooling fluid officially recognize by automotive manufacturers Technical data Type Voltage Electrical power Weight Nominal air flow Heating capacity L depth see 3 step 2 ARIZONA 600 12 24 V 150 W 2 3 kg 380 m h 6 10 kW 227 mm ARIZONA 400 12 24 V 120 W 2 kg 285 m h 5 00 kW 218 mm ARIZONA 300 12 24 V 55 W 2 kg 200 m h 4 35 kW 218 mm Optimum heating capac...

Page 4: ...ith 8 not supplied screws Blower motor axis should rather be in horizontal position on the vehicle Do not drill heater s body so as not to damage heat exchanger Connect water input and output by using cooling pipes with corresponding diameter Using suitable clamping rings Check for leaks in water Fixation stand 2 3 235 x 170 mm cut out 8 not supplied screws 8 Ø 3 7 mm Clamping rings Inlet pipe 3 3...

Page 5: ... Replace cable Check for correct cable routing and connections according to the circuit diagram Electrical connections reversed Check connecting wires according to the circuit diagram and if necessary assemble correctly Blower switch defective Replace the switch with a new original component Blockage in fan unit Rectify cause of blockage e g object in impeller If necessary order new unit Blower no...

Page 6: ... to the maximum Water flow rate through heat exchanger is too low Water lines kinked or squashed Relay hoses Water pump pressure too low see above for action Flush out water circuit Air in heat exchanger When the pumping pressure is sufficient the heater is self bleeding Install additional or more powerful water pump Unit is underdimensioned Install a more powerful unit Insufficient pumped water p...

Reviews: