Connect double poles connector according to the following circuit diagram. Use at least 1,5 

mm² cable cross-section. 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 

 
  Heater 

 

Fuses values : 

 

Voltage 

12 V 

24 V 

ARIZONA 600 

15 A 

7,5 A 

ARIZONA 400 

10 A 

5 A 

ARIZONA 300 

5 A 

3 A 

 

 

4 - Trouble shooting 

 

Fault found 

Possible cause 

Action to take 

Check  fuse  position  and  amperage.  If  necessary 
replace  it.  Before  renew  a  fuse,  always  identify 
causes.  

Fuse defective 

Examine blowers for a blockage or another type of 
defect and rectify the cause. 
Switch on ignition and/or  main battery switch. 
Check battery connections. 

No vehicle power 

Check vehicle operating instructions for possible 
advice. 

Connecting cable 
damaged or torn out 

Replace cable. Check for correct cable routing and 
connections according to the circuit diagram. 

Electrical connections 
reversed 

Check connecting wires according to the circuit 
diagram and if necessary assemble correctly. 

Blower switch defective 

Replace the switch with a new original component. 

Blockage in fan unit 

Rectify cause of blockage, e.g. object in impeller. If 
necessary order new unit. 

Blower not working 

Blower motor defective 

Replace plastic part + motor. 

No blower power 

Check connection on blower switch. 

Blower doesn’t operate 
at all speeds 

Defective resistance 

Replace plastic part + motor. 

Blower only runs at low 
and middle speed 

Fuse defective 

Replace fuse. 

Unit cannot be switched 
off 

Short-circuit in cable 

Rectify circuit diagram. If necessary, install new 
cable. 

 

12 V 

24 V 

Resistors 

Resistors 

Motor

 

Motor

 

Fuse  
(see table below) 

Black wire 

Blue wire

 

Red wire 

 High speed

 

Red wire 

 High speed

 

 

Yellow wire : low speed 
Orange wire : middle speed 

 

Yellow wire : low speed 
Orange wire : middle speed 

Thermo-fuse 

Thermo-fuse 

Fuse  
(see table below) 

Summary of Contents for ARIZONA

Page 1: ... Ind B Page 1 of 6 ARIZONA 1 Device description 2 Operation 3 Mounting information 4 Trouble shooting 5 Security advice SIROCO S A S 10 rue Jean Rostand Z I BP 315 69745 GENAS Cedex Tel 33 0 4 78 90 96 96 Fax 33 0 4 78 90 15 98 www siroco fr ...

Page 2: ...knob ARIZONA s front plate is available in different colors white grey anthracite or black Heater can be equipped with 600 400 or 300 blower that supplied in 12 V or 24 V with connections pipes diameters of 16 mm Product part numbers ARIZONA 600 ARIZONA 400 ARIZONA 300 Voltage Front plate color Part number Part number Part number White 0120 0001 0120 0101 0120 0201 Grey 0120 0002 0120 0102 0120 02...

Page 3: ...d anticorrosive for copper and aluminum Use a cooling fluid officially recognize by automotive manufacturers Technical data Type Voltage Electrical power Weight Nominal air flow Heating capacity L depth see 3 step 2 ARIZONA 600 12 24 V 150 W 2 3 kg 380 m h 6 10 kW 227 mm ARIZONA 400 12 24 V 120 W 2 kg 285 m h 5 00 kW 218 mm ARIZONA 300 12 24 V 55 W 2 kg 200 m h 4 35 kW 218 mm Optimum heating capac...

Page 4: ...ith 8 not supplied screws Blower motor axis should rather be in horizontal position on the vehicle Do not drill heater s body so as not to damage heat exchanger Connect water input and output by using cooling pipes with corresponding diameter Using suitable clamping rings Check for leaks in water Fixation stand 2 3 235 x 170 mm cut out 8 not supplied screws 8 Ø 3 7 mm Clamping rings Inlet pipe 3 3...

Page 5: ... Replace cable Check for correct cable routing and connections according to the circuit diagram Electrical connections reversed Check connecting wires according to the circuit diagram and if necessary assemble correctly Blower switch defective Replace the switch with a new original component Blockage in fan unit Rectify cause of blockage e g object in impeller If necessary order new unit Blower no...

Page 6: ... to the maximum Water flow rate through heat exchanger is too low Water lines kinked or squashed Relay hoses Water pump pressure too low see above for action Flush out water circuit Air in heat exchanger When the pumping pressure is sufficient the heater is self bleeding Install additional or more powerful water pump Unit is underdimensioned Install a more powerful unit Insufficient pumped water p...

Reviews: