2 - Operation 
 

Cooling water, beforehand heated by the vehicle, run on coil. In the same time, fan unit blows fresh 
air through the heat exchanger. Then, air temperature rise up. Finally, air output evacuate hot air.  
 

Operating conditions: 

 
Product must be on a ventilated place. 
Operating temperature have to be between -30°C and +80°C. 
Cooling  fluid  must  be  antifreeze  and  anticorrosive  for  copper  and  aluminum.  Use  a  cooling  fluid 
officially recognize by automotive manufacturers. 

 

Technical data: 
 

Type 

Voltage 

Electrical 

power 

Weight 

Nominal air 

flow 

Heating 

capacity 

L depth 

(see §3 step 2) 

ARIZONA 600 

12/24 V 

150 W 

2,3 kg 

380 m³/h 

6,10 kW 

227 mm 

ARIZONA 400 

12/24 V 

120 W 

2 kg 

285 m³/h 

5,00 kW 

218 mm 

ARIZONA 300 

12/24 V 

55 W 

2 kg 

200 m³/h 

4,35 kW 

218 mm 

Optimum  heating  capacity  is  reached  with  air  inlet  temperature  of  0°C,  nominal  air  flow  of  0,5  m

3

/h,  free  ethylene  glycol 

water and water inlet temperature of 100°C. 

 
3 - Mounting information 
 

 
        

Fix front plate on heater by using 4 supplied srews (3x15mm). Then, clip control knobs on 

its location. 
 

 

 

Front plate 

 

4 screws (3x15 mm) 

Control 
knobs 

ARIZONA 
heater 

8 x ø 3,5 mm 

 

Summary of Contents for ARIZONA

Page 1: ... Ind B Page 1 of 6 ARIZONA 1 Device description 2 Operation 3 Mounting information 4 Trouble shooting 5 Security advice SIROCO S A S 10 rue Jean Rostand Z I BP 315 69745 GENAS Cedex Tel 33 0 4 78 90 96 96 Fax 33 0 4 78 90 15 98 www siroco fr ...

Page 2: ...knob ARIZONA s front plate is available in different colors white grey anthracite or black Heater can be equipped with 600 400 or 300 blower that supplied in 12 V or 24 V with connections pipes diameters of 16 mm Product part numbers ARIZONA 600 ARIZONA 400 ARIZONA 300 Voltage Front plate color Part number Part number Part number White 0120 0001 0120 0101 0120 0201 Grey 0120 0002 0120 0102 0120 02...

Page 3: ...d anticorrosive for copper and aluminum Use a cooling fluid officially recognize by automotive manufacturers Technical data Type Voltage Electrical power Weight Nominal air flow Heating capacity L depth see 3 step 2 ARIZONA 600 12 24 V 150 W 2 3 kg 380 m h 6 10 kW 227 mm ARIZONA 400 12 24 V 120 W 2 kg 285 m h 5 00 kW 218 mm ARIZONA 300 12 24 V 55 W 2 kg 200 m h 4 35 kW 218 mm Optimum heating capac...

Page 4: ...ith 8 not supplied screws Blower motor axis should rather be in horizontal position on the vehicle Do not drill heater s body so as not to damage heat exchanger Connect water input and output by using cooling pipes with corresponding diameter Using suitable clamping rings Check for leaks in water Fixation stand 2 3 235 x 170 mm cut out 8 not supplied screws 8 Ø 3 7 mm Clamping rings Inlet pipe 3 3...

Page 5: ... Replace cable Check for correct cable routing and connections according to the circuit diagram Electrical connections reversed Check connecting wires according to the circuit diagram and if necessary assemble correctly Blower switch defective Replace the switch with a new original component Blockage in fan unit Rectify cause of blockage e g object in impeller If necessary order new unit Blower no...

Page 6: ... to the maximum Water flow rate through heat exchanger is too low Water lines kinked or squashed Relay hoses Water pump pressure too low see above for action Flush out water circuit Air in heat exchanger When the pumping pressure is sufficient the heater is self bleeding Install additional or more powerful water pump Unit is underdimensioned Install a more powerful unit Insufficient pumped water p...

Reviews: