Sinus Jevi Electric Heating B.V.
Aambeeld 19
1671 NT Medemblik
The Netherlands
tel. +31 (0)227-549 100
INSTALLATION, OPERATION AND
MAINTENANCE INSTRUCTIONS
TYPE SR-8600
EXPLOSION PROOF COLUMN RADIATOR - SR-8600
Page 8 of 21
The radiator is supplied with floor supports and wall fastening brackets.
Two floor supports are usually used for supporting the radiator lengths longer than 1150 mm. Four suspension
brackets are used for fastening against the wall. The standard coating of the steel parts consist of a shop primer and
an air-drying top coat of paint in the colour grey according to RAL 7032.
Special types of paint and colours can be supplied upon request.
1.2.2 Temperature regulation
The electric column radiator type SR8600 does not have a temperature regulation of its own. The ambient
temperature can be regulated by connecting a seperate flameproof room thermostat type ERT10.
(See documentation thermostat type ERT).
Temperature range of the thermostat can be set between 0 - 40°C.
The thermostat has a switching capacity of 16 Amp. 230 Volt and 10 Amp. 400 Volt.
The radiator can be switched directly at a tension of 400 Volt AC.
1.2.3 Technical data
For type, capacity and dimensions we refer to the documentation.
Maximum voltage: 690 Volt, standard 230 Volt.
Ex code: Ex de IIC T4 or T5 Gb, stof: Ex tb IIIC T125°C or 90°C Db
Temperature regulation by seperate thermostat type ERT10. 0 - 40°C.
Cable gland: flameproof M20 x 1.5.
Temperature safeguard with a built-in capillary thermostat with manual reset between 125°C and 135°C (or T5, 90°C).
Weight, incl. water/glycol:
SR8600/1500, 62 kg
SR8600/2000, 80 kg
SR8600/2500, 98 kg
SR8600/3000, 113 kg
1.2.4 Documentation
See documentation “Explosion Proof Column Radiator type SR8600”.