User Manual
EM303A General Purpose Inverter
88
No.
Function
Range
Unit
Default
Type
F0-28
Default Control
0: Disabled
1: Defaults Reset
0
〇
F0-29
Parameter Setting Control
0: Parameter setting permitted
1: Parameter lock 0
2: Parameter lock 1
0
●
Reset Default
F0-28=1 Reset Default:
Except motor parameters in Group F1 and FA, inverter
parameter in Group Fd, and F4-28 application macros, the parameters will
reset to default. After reset completed, F0-28=0.
Parameter Lock
F0-29=0
All parameters are allowed to be edited.
F0-29=1Parameter lock 0
:
Lock parameters except numeric settings. The numeric settings are primary
numeric frequency setting F0-07, auxiliary numeric frequency setting F9-06,
jog running frequency F0-11, preset speed 1~15(F3-00
~
F3-14), PID
numeric setting F4-01, preset PID setting 1~7(Fb-20
~
Fb-26), numeric
torque current F5-12, and preset torque setting 1~7(F5-15
~
F5-21).
F0-29=2Parameter locked 1:
Lock all parameters except F0-29. Inverter will remain the setting before
unlocked.
No.
Function
Range
Unit
Default
Type
F0-30
Inverter Model
0: Model G 1: Model P
0
〇
F0-30=0
Set inverter as Model G which is applicable to mechanical or constant torque
load.
F0-30=1
Set inverter as Model P which is applicable to square or cubic torque load
like blower, and water pump.
★
Set inverter as Model P, applicable motor power detailed on the Nameplate.
Note: The constant torque load is not applicable to Model P.
No.
Function
Range
Unit
Default
Type
F0-31
User Password
0
~
65535
XXXX
〇
F0-31
Set a new password to start password protection and prevent unqualified
personnel from editing the inverter parameters incorrectly. When password is
0, the password function is disabled.
7.2
Group F1: Motor Parameters
No.
Function
Range
Unit
Default
Type
F1-00
Motor Type
0: AC induction motor
1: Not used
0
〇
F1-01
Motor Rated Power
0.40
~
480.00 kW
XXXX
〇
F1-02
Motor Rated Voltage
60
~
660 V
XXX
〇