Fan Coil Unit Wall Mounted Type
21
(4) The min. distance from the unit and combustive surface is 1.5m.
(5) The appliance shall be installed in accordance with notional wiring regulations.
(6) An all-pole disconnection switch having a contact separation of at least 3mm in all poles
should be connected in fixed wiring.
Note:
●
Make sure that the Live wire or Zero line as well as the earth wire in the family power socket
can not be wrong connected, there should be reliable and no short circuit in the diagram.
●
Wrong connection may cause fire.
7.5 Ground requirements
(1) Air conditioner is type I electric appliance, thus please do conduct reliable grounding
measure.
(2) The yellow-green two-color wire in air conditioner is ground wire and cannot be used for
other purpose. Cut off and fixed by screw as grounded is not permissible, otherwise is would cause
serious damage.
(3) The earth resistance should follow the local code.
(4) The power source must offer reliable grounding terminal. Make sure not to connect the
ground wire with the following:
①
Tap water pipe.
②
Gas pipe.
③
Contamination pipe.
④
Other places that professional
personnel consider unreliable.
(5) The type and rated values of fuse is justified according to the silk print on the fuse or PCB.