Technical Information
Service Manual
(6) Common Protection Functions and Fault Display under COOL, HEAT, DRY and AUTO Modes
Overload protection
T
tube
: measured temperature of outdoor heat exchanger under cooling mode; and measured temperature of indoor heat
exchanger under heating mode.
1) Cooling overload
a.If T tube52°C, the unit will return to its original operation state.
b.If T tube55°C, frequency rise is not allowed.
c.If T tube58°C, the compressor will run at reduced frequency.
d.If T tube62°C, the compressor will stop and the indoor fan will run at preset speed.
2) Heating overload
a.If T tube50°C, the unit will return to its original operation state.
b.If T tube53°C, frequency rise is not allowed.
c.If T tube56°C, the compressor will run at reduced frequency.
d.If T tube60°C, the compressor will stop and the indoor fan will blow residue heat and then stop.
Exhaust temperature protection of compressor
If exhaust temperature 98
, frequency is not allowed to rise.
If exhaust temperature 103
, the compressor will run at reduced frequency.
If exhaust temperature 110
, the compressor will stop.
If exhaust temperature 90
and the compressor has stayed at stop for at least 3 minutes, the compressor will resume its
operation.
Communication fault
If the unit fails to receive correct signals for durative 3 minutes, communication fault can be justified and the whole system
will stop.
Module protection
Under module protection mode, the compressor will stop. When the compressor remains at stop for at least 3 minutes, the
compressor will resume its operation. If module protection occurs six times in succession, the compressor will not be started
again.
Overload protection
If temperature sensed by the overload sensor is over 115 , the compressor will stop and the outdoor fan will stop with a
time lag of 30 seconds. If temperature is below 95
, the overload protection will be relieved.
If voltage on the DC bus is below 150V or over 420V, the compressor will stop and the outdoor fan will stop with a time
lag of 30 seconds. When voltage on the DC bus returns to its normal value and the compressor has stayed at stop for at least
3 minutes, the compressor will resume its operation.
Faults of temperature sensors
(5) AUTO Mode
1.Operation way of AUTO mode:
:
a.When Tambient26
℃
, it will run in cooling mode. The implied set temperature is 25
℃
(note: the set temperature sending to outdoor
unit is 25
℃
).
b.For heating and cooling unit, when Tambient(19
℃
+Tsupplementary), it will run in heating mode. The implied set temperature is 20
℃
;
for cooling only unit, when Tambient22
℃
, it will run in fan mode and the displayed set temperature is 25
℃
.
c.For heating and cooling unit, when (19
℃
+Tsupplementary)
<
Tindoor ambient
<
26
℃
(for cooling only unit, 22
℃<
Tindoor ambient
<
26
℃
), it will keep the original running mode. If the unit is energized for the first time, it will run in fan mode.
2.Protection
a. In cooling operation, protection is the sam e as that under the cooling mode;
b. In heating operation, protection is the same as that under the heating mode;
c. When ambient temperature changes, operation mode will be converted preferentially. Once started, the compressor willremain
unchanged for at least 6 minutes.
Note: T
indoor amb.
indicated in 1 and 2 refers to, under initially heating mode, the indoor ambient temperature before the
command to start the compressor is performed according to the program, or after the unit is withdrawn from defrost, the
indoor ambient temperature before the defrost symbol is cleared.
Total current up and frequency down protection
If the total current I
total
W, frequency rise will be allowed; if I
total
X, frequency rise will not be allowed; if I
total
Y, the
compressor
will run at reduced frequency; and if I
total
Z, the compressor will stop and the outdoor fan will stop with a time lag of 30s.
(4) Fan Mode
Under the mode, the indoor fan will run at preset speed and the compressor, the outdoor fan, the four-way valve and the
electric heater will stop.
Under the mode, temperature can be set within a range of 16 - 30
.
Summary of Contents for ASH-09AIM PT
Page 1: ...SERVICE MANUAL ASH 09AIM PT ASH 13AIM PT MATRIX SERIE ...
Page 2: ......
Page 12: ...7 Technical Information Service Manual 596 354 838 899 303 378 550 Unit mm ASH 13AIM PT ...
Page 79: ......
Page 80: ...PARTS GUIDE MATRIX SERIE ASH 09AIM PT ASH 13AIM PT ...
Page 82: ...Service Manual Exploded View and Parts List ASH 09AIM PT ...
Page 84: ...Service Manual ASH 13AIM PT ...
Page 86: ...Service Manual Outdoor Unit ASH 09AIM PT ...
Page 88: ...Service Manual ASH 13AIM PT ...