Technical Information
Service Manual
The condition and process of defrosting
When frost is detected in the condenser, the system will enter into defrosting state. When defrosting starts, the compressor and
indoor fan will stop, and the outdoor fan and four-way valve will delay 30 seconds to stop. The compressor will start after 15 seconds
and then defrosting will be started. When the compressor has run for 7 minutes or defrosting is finished, the compressor will stop.
After 30 seconds the four-way valve opens and after another 60 seconds, the compressor and outdoor fan resume running. The
indoor fan will delay 3 minutes to run at the latest .The Heat indicator will be off for 0.5 second in each 10 seconds during defrosting.
Protection function
Anti-cold-wind protection
In HEAT mode, in order to prevent the indoor unit from blowing out cold wind, each time the compressor starts, the indoor fan
will delay 3 minutes after the compressor to run at the latest and it can adjust fan speed automatically when temperature is low.
Overcurrent protection
Overcurrent protection is the same with that in COOL mode.
(3) HEAT mode
The condition and process of heating
If T
amb
T
preset
+2C , HEAT mode will act, the compressor, outdoor fan and reversal valve will run, the indoor fan will delay
3min to stop at the latest
If T
preset
+2C < T
amb
< T
preset
+5C ,the unit will keep running in the original mode.
If T
amb
T
preset
+5C , the compressor will stop, the outdoor fan will delay 30sec to stop and indoor fan will blow 60S at low
speed, the fan speed cannot be shifted within blow residual heat.
In this mode, the temperature setting range is 16
~30C.
The air conditioner will adjust the running frequency of the compressor automatically according to the change of ambient
temperature.
When the unit is turned off in HEAT mode, or switched to other mode from HEAT mode, the four-way valve will be powered
of
When compressor is running (not including each malfunction and protection):
a.When outdoor ambient temperature20
℃
and indoor fan speed is low or medium, the fan speed will turn to high; if indoor
fan speed is high or super high, it will keep the same.
b.When outdoor ambient temperature18
℃
, the fan speed will resume set fan speed.
c. When 18
℃<
outdoor ambient temperature
<
20
℃
, it will run at present fan speed (set fan speed or high fan speed); but
when first exiting cold air prevention after entering heating mode, it will run in set fan speed.
f after the compressor stops.
3.Protection
Cold air prevention
The unit is started under heating mode (the compressor is ON):
In the case of T
indoor amb.
<24
: if T
tube
40
and the indoor fan is at stop state, the indoor fan will begin to run at low
speed with a time lag of 2 minutes. Within 2 minutes, if T
tube
40
, the indoor fan also will run at low speed; and after
1-minute operation at low speed, the indoor fan will be converted to operation at preset speed. Within 1-minute low speed
operation or 2-minute non-operation, if T
tube
42
, the fan will run at present speed.
In the case of T
indoor amb.
24
: if T
tube
42
, the indoor fan will run at low speed, and after one minute, the indoor fan
will be converted to preset speed. Within one-minute low speed operation, if T
tube
42
, the indoor fan will be converted
to preset speed.
T
preset
+5
T
preset
+2
Stop heating
Original operating status
Start heating
Run
Indoor fan
valve
Outdoor fan
Compressor
Stop
min.
min.
min.
T
amb
.
.
n
i
m
.
n
i
m
preset wind
preset wind
Reversing
The period of defrosting
Four-way valve
Compressor
Outdoor Unit
30s
30s
15s
30s
60s
Indoor Unit
7min
3min Set fan speed
Run
Stop
Summary of Contents for ASH-09AIM PT
Page 1: ...SERVICE MANUAL ASH 09AIM PT ASH 13AIM PT MATRIX SERIE ...
Page 2: ......
Page 12: ...7 Technical Information Service Manual 596 354 838 899 303 378 550 Unit mm ASH 13AIM PT ...
Page 79: ......
Page 80: ...PARTS GUIDE MATRIX SERIE ASH 09AIM PT ASH 13AIM PT ...
Page 82: ...Service Manual Exploded View and Parts List ASH 09AIM PT ...
Page 84: ...Service Manual ASH 13AIM PT ...
Page 86: ...Service Manual Outdoor Unit ASH 09AIM PT ...
Page 88: ...Service Manual ASH 13AIM PT ...