Page 71
9.2 CONTROLLER ERROR MESSAGE TABLE
MCU Error
Message
Meaning
Remedy
NOP
No motor
power
l
Verify that the ‘Emergency Power Shutoff Switch’ button
on the SCU is released.
l
Verify that circuit breaker inside the MSCU is switched
off caused by an error
l
Check the main power source in the building.
ECD
No Encoder
Signal
Check the encoder line connections to the actuators and
servo controllers
FLT
Fault
l
Motor controller module may have a fatal damage if this
happens repeatedly.
l
Replace the controller module, if necessary.
OVC
Over Current
l
This error occurs when excessive current flows through
the controller and motor. It can occur due to the
following reasons:
a. the actuators are overloaded because of excessive
movement.
b. The actuator has a mechanical problem causing
excessive friction and/or abnormal vibration.
c. too much grease is put in.
l
Replace the controller module or actuator as deemed
necessary.
OVT
Over
Temperature
l
This error appears when the temperature of the power
module on the controller is too high.
l
Replace the controller module, if necessary.
OVV
Over Voltage
l
This error appears when output voltage from the
Rectifier on the controller exceeds the standard voltage.
l
Check the input voltage value.
l
Replace the controller module, if necessary.
BLS
Bottom Sensor
Error
TLS
Top Sensor
Error
l
The actuator is extending or retracting beyond it’s
normal range of motion and is tripping the Limit
Sensors on the upper and bottom stroke limits of each
actuator.
l
Verify that the sensors are functioning properly.