ELECTRICAL RATINGS

INPUT POWER: 12OV AC 60Hz
MOTOR OUTPUT MAXIMUM: 8AMPS
FUSED: 8AMP 125V
LOW VOLTAGE SUPPLY FOR OFF BOARD CONTROLS: 12VDC @250mA

DIAGNOSTIC LED’S

GREEN POWER LED ON - POWER AND FUSE CONNECTIONS ARE GOOD
YELLOW STOP LED ON - ACTIVE STOP SIGNAL (CONTROL IS LOCKED)
RED SAFETY LED ON - ACTIVE REVERSING DETECTOR SIGNAL. (CONTROL WILL LOCK DOOR IN OPEN 
     DIRECTION)

TROUBLE SHOOTING

PROBLEM - NO RESPONSE FROM CONTROL

1) IF THE GREEN POWER LED IS NOT ON: CONFIRM THAT THERE IS 120VAC ON THE POWER INPUT AND THAT
    THE CONNECTIONS ARE CORRECT.
    CHECK THE FUSE.
2) IF THE GREEN POWER AND YELLOW STOP LEDS ARE ON: CHECK THAT THE STOP JUMPER IS CONFIGURED 
    CORRECTLY.
    CHECK CONNECTIONS TO THE STOP BUTTON.
3) IF THE GREEN POWER LED IS ON AND THE YELLOW STOP AND RED SAFETY LED’S ARE OFF: CHECK THE 
    CONNECTIONS TO THE MOTOR.
    TEST THE MOTOR DIRECTLY WITH A TEST SWITCH.
    CHECK THE MOTOR LIMITS (TURN BOTH LIMITS PLUS 5 REVOLUTIONS).

PROBLEM - MOTOR LOCKED IN ONE DIRECTION

 

1) IF THE RED SAFETY LED IS ON: CHECK THE CONNECTIONS TO THE REVERSING DETECTORS.
    CONFIRM THAT THE JUMPERS JP3 AND JP4 ARE CONFIGURED CORRECTLY.
2) IF THE RED SAFETY LED IS NOT ON: CHECK THE CONNECTIONS TO THE MOTOR.
    CHECK THE MOTOR LIMIT (TURN IT PLUS 5 REVOLUTIONS).
    TEST THE MOTOR DIRECTLY WITH A TEST SWITCH.

PROBLEM - MOTOR RUNS ONLY AS LONG AS SWITCH IS HELD DOWN

THIS IS CORRECT OPERATION IF REVERSING DETECTORS ARE NOT USED. IF REVERSING DETECTORS ARE USED, 
CHECK THE POSITION OF THE RUN TIME JUMPER (JP1 TOP).

INSTALLERS MANUAL
PAGE: 5 OF 5

Summary of Contents for SMC

Page 1: ...ports normally open and close inputs from reversing detectors ASupports 2 and 4 wire safety edges AThe stop button is selectable normally open or normally close QControl is selectable timed run or continuous pressure ASequencing input supports single contact devices such as Radio Controls Key Switches Card Readers The Smart Motor Control SMC is an ideal general purpose intelligent control system f...

Page 2: ...ECTOR CONTROLS ARE DEACTIVATED IN THIS MODE 2 THE SEQUENCING CONTROL IS DEACTIVATED IN THIS MODE 3 THIS MODE CAN BE USED TO CLOSE THE DOOR IF THERE IS A MALFUNCTION IN THE REVERSING DETECTORS THIS MUST ONLY BE DONE IF THE UP DOWN SWITCH IS IN DIRECT VIEW OF THE DOOR THE REVERSING DETECTORS MUST BE SERVICED AS SOON AS POSSIBLE AND THE DOOR RETURNED TO ITS NORMAL OPERATING MODE JUMPER OFF CONT WITH ...

Page 3: ...D WILL CAUSE THE SMC TO NOT OPERATE REVERSING DETECTOR JUMPERS JP3 JP4 JP3 JP4 JUMPERS OFF 4 WIRE EDGE BOTH JUMPERS JP3 AND JP4 MUST BE OFF TO USE A 4 WIRE SENSING EDGE NOTES 1 IF EITHER JUMPER IS OFF WITHOUT A 4 WIRE SENSING EDGE ATTACHED THE RED SAFETY LED WILL LIGHT AND THE DOOR WILL BE LOCKED IN THE UP DIRECTION BOTH JUMPERS JP3 AND JP4 SHOULD BE ON IF A NORMALLY OPEN REVERSING SENSOR IS USED ...

Page 4: ...UTTON STATION SEQ SEQ 12 12 GND GND N O SEQ SEQ 12 12 GND GND 1 2 3 RED WHITE BLACK RECEIVER SEQUENCING CONTROL SINGLE CHANNEL RADIO NOTES 1 CAN BE USED WITH ANY MOMENTARY DRY CONTACT SUCH AS KEY SWITCHES CARD READERS RADIO CONTROLS ETC 2 TWO OR MORE SWITCHES CAN BE WIRED IN PARALLEL 3 CONTROL WILL FOLLOW A SEQUENCE WITH EACH PULSE UP STOP DOWN STOP UP NOTES 1 WIRING SHOWN IS STANDARD BUT MAY VARY...

Page 5: ...ES UPON SENSING EDGE ACTIVATION WHEN THE DOOR IS GOING UP INSTEAD OF DOWN REVERSE THE RED AND BLACK MOTOR LEADS JP1 JP1 N O SENSING EDGE 2 WIRE JP3 JP4 N O SE2 SE2 SE1 SE1 NC NC NO NO MOM MOM CONT CONT JP1 JP1 NOTES 1 JUMPER JP3 MUST BE ON AND JP4 MUST BE OFF WHEN USING NORMALLY CLOSE REVERSING SENSOR 2 JP1 TOP JUMPER MUST BE OFF CONT THIS SETS THE SMC RUN TIMER ON 3 JP1 LOWER JUMPER SETTING DEPEN...

Page 6: ... AND YELLOW STOP LEDS ARE ON CHECK THAT THE STOP JUMPER IS CONFIGURED CORRECTLY CHECK CONNECTIONS TO THE STOP BUTTON 3 IF THE GREEN POWER LED IS ON AND THE YELLOW STOP AND RED SAFETY LED S ARE OFF CHECK THE CONNECTIONS TO THE MOTOR TEST THE MOTOR DIRECTLY WITH A TEST SWITCH CHECK THE MOTOR LIMITS TURN BOTH LIMITS PLUS 5 REVOLUTIONS PROBLEM MOTOR LOCKED IN ONE DIRECTION 1 IF THE RED SAFETY LED IS O...

Reviews: