Configuration and setup
20221495F
101
Drive unit voltage
Set the drive unit voltage to correct level. The selections are
12V, 24V, or 32V and should be set to the voltage specified for
your drive unit.
Refer to the drive unit table on page 72 for information.
The drive engage/bypass clutch output follows the same voltage
as set for the drive unit. It is not possible to select a higher
voltage than the input voltage.
Caution !
Selection of improper voltage level for your drive unit may
damage both the drive unit and the autopilot computer even if
the protection circuits in the autopilot computer are activated.
During the Rudder Test, the AP25 system will automatically
detect whether the drive unit is a reversible motor or a solenoid
is operated.
To change the voltage
selection, rotate the course
knob.
Note !
The drive unit voltage setting does not apply when operating
solenoids on a continuous running pump/steering gear. Hence,
the output voltage to the solenoids will be the same as the input
voltage.
Proceed to next menu item by pressing
STBD
button.
Rudder Feedback Calibration
Make sure the RF300 is installed and aligned as pr. instruction in
section 3.6 (or eventually section 3.27 for LF3000). This
function enables you to compensate for any non-linearity in the
transmission between the rudder and the rudder feedback.
Summary of Contents for AP25
Page 1: ...MANUAL SIMRAD AP25 Autopilot 20221495F Sw 1 3 English ...
Page 2: ......
Page 48: ...Simrad AP25 Autopilot 46 20221495F 1 2 4 3 7 5 6 8 Figure 2 2 Wind steering ...
Page 66: ...Simrad AP25 Autopilot 64 20221495F This page is intentionally left blank ...
Page 140: ...Simrad AP25 Autopilot 138 20221495F This page is intentionally left blank ...
Page 172: ...Simrad AP25 Autopilot 170 20221495F wind vane steering 41 Z zigzag turn 27 55 ...