REV020620
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 |
| 10 |
7.
After securely placing all the battery modules in the BOSS.6 Enclosure, confirm that all the battery
module circuit breakers are still in the “OFF” position.
8.
Attach negative interconnecting busbars onto the batteries’ negative terminals. Secure the busbars to
the batteries’ terminals using a 11/16” wrench socket to tighten the 3/8” flat washers (included with
cabinet), 3/8” lock washers and 11/16” stainless steel hex nuts (originally included on the batteries).
Tighten the nuts to 160 in-lbs.
9.
Attach positive interconnecting busbars directly onto the batteries’ positive terminals. Secure the
busbars to the batteries’ terminals using a 11/16” wrench socket to tighten the 3/8” flat washers
(included with cabinet), 3/8” lock washers and 11/16” stainless steel hex nuts (originally included on
the batteries). Tighten the nuts to 160 in-lbs.
Interconnecting busbars are not included with Enclosure.
Positive battery terminals are
nearest the bottom of the
enclosure. Posts point towards
the Enclosure’s door.