OPERATION
1. Connect a ground cable from the
truck to the provided ground stud.
2. Unlock
the
fi ll box and connect a
delivery hose to the hose coupling.
3. Turn the Control Power switch to
the ON position.
4. Select the tank to fi ll using F1 or F2
on the digital display.
5. Press F4 on the digital display to
open the fi ll valve for the selected
tank. (Only one fi ll valve may be
open at a time.)
6. The
fi ll valve opens, and the pump
starts.
7. Open the valve on the truck.
8. Start the delivery pump on the truck
(if applicable).
9. Fuel is delivered to the tank.
10. Delivery may be stopped at any
time by pressing F5 on the digital
display to close the fi ll valve and
stop the pump.
11. When the Tank Full level is reached,
an alarm will be displayed and the
tank fi ll valve will close. To reopen
the valve for 30 seconds, press F3
to override the high fuel level and
top off the tank or drain the hose.
12. When the Tank High level is
reached, an alarm will be displayed;
the fi ll valve will close and cannot
be reopened until the fuel level falls
below high level.
13. If any tank in the system reaches
the Critical High level, an alarm will
be displayed and no fi ll valves will
be allowed to open.
14. During a fi lling operation, if any tank
not selected for fi lling reaches Full,
High or Leak, the selected tank’s
fi ll valve will close. At this point the
operator can reopen the selected
fi ll valve if desired.
15. Stop the delivery pump on the truck.
16. Close the valve on the truck.
17. Drain the delivery hose.
18. When the fi lling operation is com-
plete, press F5 to close the fi ll valve
and stop the pump.
19. Disconnect the delivery hose.
20. Turn the Control Power switch to
the Off position.
21. Close and lock the fi ll box.
22. Fuel delivery is complete; discon-
nect the ground cable from the
trucker’s grounding stud.
TO DRAIN WITH
MOTOR-PUMP
1. Start the pump by pressing F4 on the
digital display. If the high fuel alarm
is activated, press F3 on the digital
display. Override is activated for 30
seconds and can be reactivated until
the critical high fuel level is reached.
2. The pump will start. Operate the hand
pump to prime the pump.
3. Open the hand pump bypass valve.
4. The pump will empty the spill basin.
Note: Full basin will be emptied in
about 20 seconds.
5. Stop the pump when the basin is
empty by pressing F5 on the digital
display.