SMARTPUMP TOUCHSCREEN OPERATION
1. Main Screen
F1 / F2 Select tank
F3 High level fi ll override
F4 Open valve to selected tank
F5 Close valve to selected tank
To access system setup, press and
hold F1+F2+F3
2. System Setup
F1 Access tank setup
F2 Calibrate transducer (factory set)
F3 Select PLC Modbus node
F4 Set PLC analog card type (factory
set)
F5 Enable/disable pump
3. Tank Setup
F1 Select next tank
F2 Set tank capacity (0 for tank not
used)
F3 Set tank inside height (0 for tank
not used)
F5 Toggle square tank / round tank
/ tank not used
4. Status Indications
Critical High Fuel
(>95%
by
fl oat)
– Fill Disabled
High
Fuel
(>90%
by
fl oat)
– Fill disabled, but may
be overridden with F3
Refi ll
(<55% by transducer)
Low
Fuel
(<10% by transducer)