background image

Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616

© 2007 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com

®

LOAD BANK MANUAL • Saturn 3000 DV • W.O. 63798/2 • page 6 of 20

PROCEDURE

1. Confirm the test source is properly

grounded and ground the Load Bank
in compliance with NEC.

2. If Remote Control is desired, using

CAT 5 Patch Cable, connect the
laptop computer to Receptacle 3 on
the Load Bank.

3. Confirm all load command switches

are in the “Off” position.

4. Confirm the Disconnect Switch

(DSW) is in the “Off” position.

5.

See Fan/Control Power Drawing
47B164462B. Connect and external
480/600V, 3ø, 60Hz, 60A source to
FCB 1A as shown.

Consult NEC for proper wire size.

6.

See Control Drawing 47B164461C.
Using #14 AWG copper wire or
greater with a torque of 35 in. lbs.,
connect customer supplied Load
Dump contacts to TB‘LD’ 1–2 or place
the “Load Dump Mode” switch in the
“Bypass” position.

Load is disengaged when the con-
tact is open.

Load is engaged when the contact is
closed.

7.

See Resistive Load Section 1 Draw-
ing 47B164469. Cable the load
source to the Load Bank as shown.

Consult NEC for proper wire size.

8. Place the Disconnect Switch (DSW)

in the “On” position.

9. Place the Fan Circuit Breakers (FCB

1A or FCB 1B) in the “On” position.

OPERATION

LOCAL

1. Place the “Load Voltage Selector”

and “Fan/Control Power Voltage Se-
lector” switches in the appropriate
positions.

2. Place the “Load Bank Mode” switch

in the “Local Manual” or “Remote”
position.

3. Start-up generator or bring other test

source on line.

If External Fan/Control Power is be-
ing used, “Fan/Control Power” switch
in the “On” position to energize the
cooling fan before starting the gen-
erator to assure proper fan opera-
tion.

4. Adjust power source voltage and fre-

quency.

5. Place the “Fan/Control Power” switch

in the “On” position to energize the
cooling fan.

A false “Cooling Failure” lamp indica-
tion may be present until the cooling
fan creates sufficient airflow to close
the Fan Pressure Switch (PS). The
“Normal Operation” lamp illuminates
and control voltage is supplied to the
“Master Load” switch. With voltage
supplied to the “Master Load” switch,
the operator is now ready to apply
load steps.

6. Verify the illumination of the “Normal

Operation” lamp before proceeding.

7. Visually observe correct fan opera-

tion and investigate any unusual fan
related noises.

8. Check air intake for obstructions and

confirm positive air flow.

Summary of Contents for Saturn 3000 DV

Page 1: ...2550KW 3000KW 480 600V 60KW Res LCL PLC INT EXT CP Powered Louvers File 63798 2 p65 Disk SDCX155 This instruction manual has been reviewed and is approved by me as being fully accurate and representat...

Page 2: ...er 63798 07 43 2 Model Saturn 3000 DV June 2007 The information herein is the property of Simplex Inc and or its subsidiaries Without written permission any copying transmitting to others and other us...

Page 3: ...cation 5 Procedure 6 OPERATION 6 Local 6 Remote 7 Load Dump 8 FAILURE DETECTION 8 Thermocouple Temperature Switch 8 MAINTENANCE 9 Each Operation 9 Every 50 Hours or 6 Months 10 Motor Lubrication 10 TR...

Page 4: ...ation is by magnetic contactor All load branch circuits areprotectedby200 000AICclass T fuses Operating controls are located on a LocalControlPanelandaRemoteCon trol Panel The Control System is com pr...

Page 5: ...safety hazard to the opera tor When a cooling failure occurs the automatic safety features in the Control System immediately remove the load from the load source The malfunction must be corrected and...

Page 6: ...ents con servativelyoperateatapproximatelyhalf the maximum temperature rating of the alloy 1080 Fvs 1920 F Forexample Alloy FeCrAl See Parts Legend Drawing for specific elements used These elements ar...

Page 7: ...in safe operation The Load Bank must be po sitionedandinstalledaccordingtolarge airflow requirements There must be a minimum clearance of6feetonallsidesoftheLoadBank Load Banks installed indoors must...

Page 8: ...Load Bank as shown Consult NEC for proper wire size 8 Place the Disconnect Switch DSW in the On position 9 Place the Fan Circuit Breakers FCB 1A or FCB 1B in the On position OPERATION LOCAL 1 Place th...

Page 9: ...e Off position REMOTE There are three screens on the remote touch panel They are Control Status Screen Load Screen and Metering Screen 1 Press the Activate Remote button 2 Press the Energize Control P...

Page 10: ...ssing these contacts and enabling the load section by flipping the Auto Load Dump switch to the Bypass position This disables the load dump featureandilluminatesthe LoadDump Bypass lamp Metering Scree...

Page 11: ...branches should be checked for blown fuses or opened load resis tors To check the fuses or load resis tors operate the Load Bank from a balanced 3 phase source and check the three line currents The t...

Page 12: ...on caused by Load Bank operation may result in loose con nections Thevibrations caused by the cooling fan may also loosen electricalconnections If the Load Bank is trans ported over the road the elect...

Page 13: ...OTING This section is designed to aid the elec trical technician in basic Load Bank systemtroubleshooting Alloftheprob lems listed can be verified with a basic test meter and or continuity tester For...

Page 14: ...t temp below EXTS setpoint 1 Restriction of air intake or exhaust 2 Fan pressure switch inoperative 3 Overtemperature sensor failure DRAWINGS AND PARTS LIST The drawings included in this manual are th...

Page 15: ...switch used to energize cooling system GFB Ground fault breaker GBTR Ground breaker tripped relay HVR High voltage relay Hz Hertz cycles per second measurement of frequency IFCV Incorrect fan control...

Page 16: ...iply the answer of step 3 times the square root of 3 1 732 5 Dividetheanswerofstep 4by1000 The answer is the actual kilowatts of loadbeingappliedbytheLoadBank Single Phase 1 Determine the line current...

Page 17: ...the desired amount of kilowatts applied at 1 0 power fac tor The following calculations are used to determine a step kilowatt rating at other than a rated voltage This is accom plishedbyreferencingth...

Page 18: ...tts 1 phase Volts x Amps x PF Volts x Amps 1000 1000 3 phase 1 732 x Volts x Amps x PF 1000 Power Factor expressed as decimal Resistive Load Bank PF is 1 0 Amperes 1 phase KW x 1000 KW x 1000 KW known...

Page 19: ...IN LBS 250 1 4 20 Grade 5 dry 8 96 250 1 4 20 Grade 2 dry 5 5 66 312 5 16 Grade 5 dry 17 204 312 5 16 Grade 2 dry 11 132 375 3 8 Grade 5 dry 30 360 375 3 8 Grade 2 dry 19 228 437 7 16 Grade 5 dry 50...

Page 20: ...5 600V 30A 8 AWG 40 T60060 3CR 4 6 AWG 45 600V 60A 2 3 AWG 50 60100 3CR 600V 100A MISCELLANEOUS TERMINALS METERS SWITCHES COILS RELAYS XFORMERS CONNECTION TORQUE SIZE INCH LBS 4 5 6 10 8 19 10 31 1 4...

Page 21: ...ated with Mobil Mobilith AW2 grease a Lithium based grease Lubrication using another grease may cause bearing failure If the lube interval is less than a month use the Weekly Relube Quantity at each r...

Page 22: ...Control 47B164465A PLC Control Wiring 47B164466B Metering 47B164467A Resistive Contactors Coil 47B164468 Load Section 1 of 3 47B164469 Load Section 2 of 3 47B164470 Load Section 3 of 3 47B164471 Load...

Reviews: