Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616
© 2007 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com
®
LOAD BANK MANUAL • Saturn 3000 DV • W.O. 63798/2 • page 7 of 20
9.
Select the desired load steps by
placing them in the “On” position.
10. Place the “Master Load” switch in
the “On” position.
This simultaneously applies all of
the load steps which are in the “On”
position.
Trim is achieved by flipping the load
steps “On” and “Off” while the “Mas-
ter Load” is in the “On” position.
11. Adjust source voltage and load.
Monitor as needed.
Shutdown
1 De-energize the load.
2. Run the cooling fan for 5 minutes to
assure a thorough cool down of all
load elements (optional).
3. Place the “Fan/Control Power” switch
in the “Off” position.
REMOTE
There are three screens on the remote
touch panel. They are: Control/Status
Screen, Load Screen, and Metering
Screen.
1. Press the “Activate Remote” button.
2. Press the “Energize Control Power”
to energize the cooling fan.
A false “Cooling Failure” may be indi-
cated until the cooling fan creates
sufficient airflow to close the Fan
Pressure Switch (PS).
3. Verify “Normal Operation” via the
status window before proceeding.
4. Visually observe correct fan opera-
tion and investigate any unusual fan
related noises.
5. Check air intake for obstructions and
confirm positive air flow.
Control/Status Screen
6.
Select the desired load steps by
pressing the desired buttons.
7.
Press the “Master Load” button.
This simultaneously applies all of
the load steps which are in the “On”
position.
Trim is achieved by pressing the
load steps “On” and “Off” while the
“Master Load” is in the “On” posi-
tion.
8.
Adjust source voltage and load.
Monitor as needed.
Load Screen